Owner manual

78 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011
Programming Master Programming Level
ANN-RLY Options
Pressing 1 for ANN-RLY Options while viewing ANN-BUS Screen #3 will cause the following
screen to be displayed:
The ANN-RLY module provides ten Form-C relays which can be programmed for various
functions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will
display the remaining relays for this module.
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option screen,
press the number key corresponding to the relay to be programmed. Following is a list of the
available programming options for each relay:
General Alarm
General Trouble
General Supervisory
Future Use
Future Use
Future Use
General Discharge
Discharge Release 1
Discharge Release 2
•AC Loss
Waterflow Delay
Future Use
Future Use
Future Use
General 2nd Shot Release
2nd Shot Release 1
2nd Shot Release 2
Input Zone 1
Input Zone 2
Input Zone 3
Input Zone 4
Input Zone 5
Input Zone 6
PROGRAMMING
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
ANN-BUS Screen #3
ANN-RLY OPTIONS
1=RELAY 1 IN ZONE 1
2=RELAY 2 IN ZONE 2
3=RELAY 3 IN ZONE 3
ANN-RLY Options Screen