Owner manual
PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 137
Maximum Number of Detectors per Zone Compatible Devices
G.2 Maximum Number of Detectors per Zone
When using two-wire smoke detectors containing supplementary relays or indicators, the operation
of more than one detector per zone cannot be ensured
Model Number Base Model
Number of
Devices
2W-B N/A 16
2WT-B N/A 16
1100/D N/A 20
1151 B401/B110LP/B116LP 16/16/1
1400 N/A 20
1451 B401B / B406B 16/ 1
1451DH DH-400 16
1800 N/A N/A
1851B B101B N/A
1851B B107B N/A
1851DH DH1851DC 16
2100/D/S N/A 16
2100T/D/S N/A 16
2151 B401/B110LP/B116LP 16/16/1
2300T N/A 16
2400 N/A 16
2400AIT N/A 1
2400AT N/A 1
2400TH N/A 16
2451 B401B / B406B 16/1
2451 DH-400 16
2451TH B401B / B406B 16/1
2800 N/A N/A
2800TH N/A N/A
2851B B101B N/A
2851B B107B N/A
2851BTH B101B N/A
2851BTH B107B N/A
2851DH DH2851DC 16
DH100P N/A 16
DH100LP N/A 16
2WTA-B N/A 1
2WTA-RB N/A 1