Owner's manual

1 The PDRP-1002/PDRP-1002E
Input Circuits
6 The PDRP-1002 PN 51135:A 03/11/99
1 The PDRP-1002/PDRP-1002E
Features
Microprocessor-controlled
Power-limited on all circuits except Municipal Box output
Alarm and trouble resound
Four Class A (Style D)/Class B (Style B) Initiating Device Circuits
Two Class A (Style Z)/Class B (Style Y) Notification Appliance circuits
Two Class B (Style Y) Release Circuits
General alarm and trouble relays
Optional module for 4 zone/function relays (4XZM)
Optional transmitter module (4XTM). Complies with NFPA 72 Auxiliary and
Remote Station Fire Alarm systems
Optional volt/amp meter module (4XMM)
Optional supervised remote annunciator (RZA-4X)
Requires LED Interface Module (4XLM)
Optional digital communicator (NOTI•FIRE 911AC)*
Complies with NFPA 72 Central Station and Remote Station Fire Alarm Systems
Supervisory Input Option
Delay timer (adjustable)
Three abort function options
Designed for suppression standards NFPA 12, 12A and 12B
Disable/enable controls per initiating zone
Last Event Recall
Battery/Earth fault supervision
Fuse protection on all Notification/Release Circuits
RMS regulated output power, 2.25 amps
7 amp/hour to 15 amp/hour battery options, up to 90 hours standby
Resettable and non-resettable regulated power outputs
Extensive transient protection
Watchdog timer to supervise microprocessor
Output circuits protected against false activations
Slide-in zone identification labels
Steel cabinet 14.5 in (368.3 mm) wide by 16 in ( 406.4 mm) high by 5 in (127 mm)
deep
Dead-front dress panel option (DP-4X)
Trim ring for flush mount between 16 in (406.4 mm) center studs (TR-4XR)
Abort and manual release circuits
Cross-zone option
*
Applications which require the NOTI•FIRE 911AC are not FM approved
.
Circuits
Input Circuits
Detector Zone 1, Class A (Style D)/Class B (Style B)
Detector Zone 2, Class A (Style D)/Class B (Style B)
Abort, Class A (Style D)/Class B (Style B)
Manual Release, Class A (Style D)/Class B (Style B)
Output circuits (optional auxiliary relays track these four circuits)
Notification Appliance Circuit 1, Class A(Style Z)/Class B (Style Y)
Notification appliance Circuit 2, Class A(Style Z)/Class B (Style Y)
Releasing Circuit 1, Class B (Style Y)
Releasing Circuit 2, Class B (Style Y)/Supervisory Input, Class B (Style B)