Owner's manual
3 Installation Procedure
Notification Appliance Circuits
18 The PDRP-1002 PN 51135:A 03/11/99
Output Circuits
Notification Appliance Circuits
This control panel can provide two Class A (Style Z)/Class B (Style Y) Notification
Appliance Circuits and two Class B (Style Y) Releasing Circuits (see section “Setting
Mode of Operation” for DIP switch configuration). Each circuit is capable of 1.5 amps
of current. Total current drawn from all four circuits cannot exceed 2.25 amps. Refer
to the Compatibility Chart. Circuits are supervised and power-limited.
Note: Wiring must be configured to maintain a minimum voltage of 20.4V on release circuits. Calculation of
maximum allowable resistance:
R
MAX
= 20.6V-20.4V
________________________________________________________________________
I
S
Where:
R
MAX
= maximum allowable resistance of wiring
I
S
= solenoid current
Figure 6 Notification Appliance Circuits
B+
B+ A+ A-
B-
B+ A+ A-
B-
NC
NC
B+ B-
B-
345 6 78910111213141516
TB2
+ -
+
-
+ -
+
-
B+ A+ A-
B-
B+
B-
RPNAC.cdr
Note: Output #4 can be configured for releasing or supervisory circuit (see Section “Setting Mode of Oper
a
configured as a releasing circuit, the circuit will be non-power limited. If configured as a supervisory circuit
,
will be power limited. All wiring must follow the power limited “General” Section.
Dummy Load all
unused Notification
Appliance Circuits
Dummy Load all
unused Releasing
Circuits
4.7K, 1/4-Watt
4.7K, 1/4-Watt
OUT #1
OUT #2
OUT #3
OUT #4
See note
below
Polarized Horn
Polarized Strobe
Polarized Bell
Class A
(Style Z)
Notification
Appliance Circuit
Class B (Style Y) Notification
Appliance Circuit
4.7K, 1/2-Watt
(part #71252 UL listed)
Releasing Circuits
UL listed & FM approved
Releasing Devices
No Connection
No Connection