3 Installation Procedure
Zones
16 The PDRP-1002 PN 51135:A 03/11/99
Initiating Device Circuits
Zones
Wire all alarm initiating devices sequentially for proper supervision. Initiating devices
include: heat, photoelectric, and ionization type detectors; and waterflow alarm
devices. Refer to the Compatibility Chart in Appendix B.
Note:
• Observe polarity when connecting polarized devices.
• All circuits are supervised and power limited.
• Leave Dummy Load (provided) on all unused circuits.
Figure 4 Example of an Alarm Initiating Device
B+ A+ A-
B-
B+ A+ A-
B-
B+ A+ A-
B-
B+ A+ A-
B-
TB4
+
+
+
+
+
+
_
_
_
_
_
_
12
3
4
56
7
8910
11 12
13
14
15 16
AIDEX.cdr
IN #1 IN #2 IN #3 IN #4
Manual
Pull Station
Heat
Detector
Two-wire
Smoke
Detector
Class B (Style B)
Initiating Device Circuit
4.7K, 1/2-Watt (part # 71252 UL listed)
Class A (Style D)
Initiating Device
Circuit
Abort Switch
4.7K, 1/2-Watt
(part # 71252
UL listed)
Manual Release
4.7K, 1/2-Watt
(part # 71252
UL listed)