1. Product Description
Overview
The PDRP-1002 Agent Release Control System has been designed as a control center for use in automatic 
fire supression systems. The panel is a feature-packed control unit suitable to perform detection and control 
functions associated with the release of gaseous agent/special hazard fire protection systems. The PDRP-
1002 is designed for maximum reliability with 100% solid state circuitry and isolated relay contacts for 
outside interfacing and features programmable options to allow on-site customization of the unit for various 
operating configurations.
An integral standby battery system, with charger, is provided.  In case of commercial AC power 
interruption, automatic switchover to the battery system will provide power to the panel for a minimum 
of 24 hours.
The FACP is supplied complete with backbox, hinged door, control switches, and indicator LEDs. 
The entire unit is housed in a standard sheet-metal enclosure with 1/2 in. (12.7 mm) and 3/4 in. (19.05 mm) 
conduit knockouts available.
The PDRP-1002 is a 110/120 VAC agent release control panel. The PDRP-1002E is a 220/240 VAC agent 
release control panel.
Features 
Options 
Note: Applications which require the 411UDAC or the NOTI-FIRE 911AC are not FM approved.
• Microprocessor-controlled
• Power-limited on all circuits except Municipal Box 
Output and Releasing Circuits
• Alarm and trouble resound
• Four Style B/D Initiating Device Circuits
• Two Style Y/Z Notification Appliance Circuits
• Two Style Y only Release Circuits
• General alarm and trouble relays
• Delay Timer (adjustable)
• Three abort function options
• Abort and manual release circuits
• Designed for supression standards
• Disable/enable controls per Initiating Device Circuit
• Last Event Recall
• Battery /Earth fault supervision
• Current protection on all notification circuits
• RMS regulated output power, 2.25 amps
• 7 amp-hour (AH) to 18 AH battery options, up to 90 
hours standby
• Resettable and nonresettable regulated power 
outputs
• Extensive transient protection
• Watchdog timer to supervise microprocessor
• Output circuits protected against false activations
• Slide-in zone identification labels
• Steel cabinet 14.5” (36.83cm) wide by 16.00” 
(40.64cm) high by 4.75” (12.07cm) deep
• 4XZM Module for 4 zone/function relays
• 4XTM Transmitter Module - Complies with NFPA 
72 Auxiliary and Remote Station Protective 
Signaling systems
• 4XMM Volt/Amp Meter Module
• RZA-4X Supervised remote annunciator (requires 
4XLM Interface Module)
• 411UDAC or NOTI•FIRE 911AC Digital 
Communicator - Complies with NFPA 72 Central 
Station and Remote Station Protective Signaling 
systems
• Cross-zone option
• Supervisory Input option
• Dead-front dress panel option (DP-4X) (Required 
for Canadian applications)
• Trim ring for flush mount between 16 in. (40.64 cm) 
center studs (TR-4XR)