Setting Mode of Operation 2. Installation
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
29
Switch #2 - Supervisory/Releasing Service
Set the function of Releasing Circuit #2 by setting this switch. 
Switch #3 and #4 - Timer Delay
Select the desired timer setting and set these switches accordingly. 
Switch # 5 and #6 - Abort Function
Select the desired Abort Functions for delaying the activation of releasing circuits, and set these switches 
accordingly. If ‘Cross Zone’ is selected, both IDC #1 and IDC #2 must be activated to start timer. 
OFF ON
REL #2 Will function as a solenoid releasing 
circuit.
Note: This circuit is nonpower-
limited.
REL #2 Will function as a supervisory input 
circuit.
• A short condition on this circuit 
will light the Supervisory LED 
and sound the supervisory tone on 
the control panel piezo.
• An open condition generates a 
circuit trouble condition.
Note: This circuit will now be power-
limited.
No Delay* 10 Second 20 Second 30 Second
Switch #3
OFF OFF ON ON
Switch #4
OFF ON OFF ON
* Abort timer will not operate when timer is set for ‘No Delay’.
Switch #5
OFF OFF ON ON
Switch #6
OFF ON OFF ON
Standard UL-type 
delay timer
IRI-type delay 
timer
NYC-type delay 
timer
Local Jurisdiction 
delay timer
Continues to count 
down upon ABORT, but 
stops and holds at 10 
seconds until release of 
the ABORT switch. 
Upon release of the 
ABORT switch, the 
timer resumes the 
countdown at 10 
seconds.
Functions the same as 
the UL-type timer with 
the exception that the 
ABORT will function 
only if pressed and held 
before 2nd zone goes 
into alarm.
When an alarm exists, 
pressing ABORT 
changes timer value to 
the Timer Delay plus 90 
seconds. The timer will 
not start while ABORT 
is held. SYSTEM 
RESET restores timer to 
origional Timer Delay. 
Each time ABORT is 
pressed again adds 90 
seconds to Timer Deley.
Once the timer has 
started, pressing 
ABORT resets the timer 
to full Timer Delay. The 
timer will not start 
while ABORT is held. 
Releasing the ABORT 
switch continues the 
countdown; pressing 
ABORT again restores 
Timer Delay to its full 
value.
Note: Abort timer will not operate when timer is set for ‘No Delay’. Manual pull station does not use 
abort mode.
These modes are the only ones that 
comply with UL Standard 864.