User manual
2. Installation Setting Mode of Operation
28
PDRP-1002 Instruction Manual PN 51135:B0  04/06/01
Setting Mode of Operation
Select operating mode by setting the SW1 DIP switches as described below; basic programming options 
are shown in this section.
After any changes are made to the configuration of the switches, the panel must be reset.
For Canadian use, refer to "Sprinkler Supervisory Tracking" on page 36. 
Figure 19 DIP Switch Settings
DIP Switch Functions
Switch #1 - Cross Zone
Select the desired mode of operation and set switch per appropriate column: 
OFF ON
NAC #1 Activated by an alarm in either 
IDC # 1 or IDC #2.
NAC #1 Pre-discharge Alarm
 - Activated by 
the first alarmed zone in the system. 
Initiation of an alarm on the other 
zone will shut this output off
NAC #2 Activated by an alarm in either 
IDC #1 or IDC #2.
Note: The NAC will pulse at 60 ppm 
while timer is running or frozen by 
abort and will sound steady upon 
release (time out).
NAC #2 Activated when alarms occur on 
both IDC #1 or IDC #2.
Note: The NAC will pulse at 60 ppm 
while timer is running or frozen by 
abort and will sound steady upon 
release (time out).
REL #1
REL #2
Will be activated when the timer expires (provided that REL #2 is functioning as a 
releasing circuit - set via DIP switch #2)
The Releasing Circuit Delay Timer will start 
whenever an alarm occurs on either IDC #1 or 
IDC #2.
The Releasing Circuit Delay Timer will start 
whenever an alarm occurs on both IDC #1 or 
IDC #2.
SW1
MS44-dipsw.cdr
Basic Programming
Switch 1: Cross Zone
Switch 2: Supervisory
Abort Options
Switch 3: Delay Timer
Switch 4: Delay Timer
Delay Timer
Switch 5: Abort Option
Switch 6: Abort Option