Manual

User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1
14
Factory Conguration
Address Size
(16-bit
words)
Parameter Name Type Description
40299 ½ SLC Interface Present bool Designates the presence of an SLC interface
(ie Eclipse, Flashscan, etc)
300 1 SLC_PROTOCOL_TYPE U16 Defines the supported SLC protocol.
CONVENTIONAL 0
CLIP 1
FLASHSCAN 2
ECLIPSE 3
ADVANCED 4
PROTOCOL_OTHER 5
301 1 OEMID_TYPE U16 Defines Device OEM.
For internal use only.
302-304 3 MAC Addr U8[6] Device’s MAC Address
Stored in the format described for MAC address storage.
305 ½ Sensor Type U8 Smoke 1
306 ½ Firmware Main Board Rev U8 Main Board Microcontroller Firmware Image Revision
307 ½ Firmware Photo 1 Rev U8 Chamber Microcontroller Firmware Image Revision
308 ½ Firmware Photo 2 Rev U8 Not used, set to zero
309 ½ Hardware Main Board Rev U8 Revision of Main Board Hardware
310 ½ Hardware Photo1 Rev U8 Revision of Photodetector Hardware
311 ½ Hardware Photo 2 Rev U8 Not used, set to zero
312 ½ Hardware Blue Rev U8 Revision of Blue LED Driver Hardware
313 ½ Hardware Laser Rev U8 Revision of Laser Driver Hardware
314 ½ Hardware UI Rev U8 Revision of User Interface Hardware
315 ½ Hardware Ultrasonics Rev U8 Revision of Ultrasonics Board Hardware
316 ½ Hardware SLC Rev U8 Revision of SLC Interface Hardware
317 ½ Photo Cal1 U8 For internal use only.
318 ½ Photo Cal2 U8 For internal use only.
319 ½ Photo Cal3 U8 For internal use only.
320 1 Blue Cal U16 For internal use only.
321 1 IR Cal U16 For internal use only.
322 ½ Airflow Boundary U8 For internal use only.
323 ½ Airflow Timer U8 For internal use only.
324-325 2 Mfg Time Stamp U32 Manufacturing Time Stamp – UNIX seconds since epoch
format
Table 6. Factory Configuration Modbus Holding Registers