FAAST Fire Alarm Aspiration Sensing Technology® Modbus USER GUIDE
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Table of Contents Product Description..........................................................................................................................3 Communication Interface.................................................................................................................4 Client Interface...............................................................................................................
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Product Description The FAAST - Fire Alarm Aspiration Sensing Technology® aspirating smoke detector is an advanced particulate detection system designed for use in early warning and very early warning fire detection applications. FAAST draws air from the environment through sampling holes in a pipe network and monitors for smoke particulates.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Communication Interface Modbus protocol stack is an application that runs over TCP. The device requires a 10 or 100Mbps Ethernet connection to an existing IP network and a valid network configuration in order to enable Modbus Communications. The FAAST device’s TCP server will listen for Modbus protocol packets on Port 502. Separate TCP ports allow Modbus, e-mail, PipeIQ and web communications simultaneously.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Device Sensor Status and Control Operations Device Read The Modbus client is able to read the device status data directly via input and holding register reads. Device Output and Operating Mode Control The Modbus client is able to initiate different operating modes through the Sensor Input Holding Register. 1.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Device Sensor Status and Control Operations (Cont’d) Device Time In order to set the time, the following steps must be followed: 1. Write the Administrator Password in the Administrator Password holding register. 2. Read the Sensor API status holding register and verify that the ADMIN_UNLOCK bit is set. If it is set, the Sensor API Command Register is enabled and will process commands issued. 3.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Reading Logs In order to read the device logs, the following steps must be followed. Event Log Read 1. Write the Administrator Password in the Administrator Password holding register. 2. Read the Sensor API status holding register and verify that the ADMIN_UNLOCK bit is set. 3. Write the Event log index value into corresponding holding register using Write Single Holding Register Command (0x06).
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Modbus Configuration The device’s Modbus Configuration Structure is READ/WRITE and mapped directly to a set of holding registers. The structure in the Firmware is defined as follows: Address Size (16-bit words) Parameter Name Type Description 40326 1 ∆ Administrator Password U16 Password to enable Commands through the Command holding register.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Holding Registers Note: The Modbus Holding Register addresses are indexed for a Honeywell Building Solutions Enterprise Building IntegratorTM client. Other clients may need to subtract 1 from each address in order to access the desired register. Device Status The device’s Device Status Structure is READ ONLY and mapped directly to a set of holding registers.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Holding Registers (Cont’d) Device Status Address Size (16-bit words) Parameter Name Type Description 8 ½ Relay Status U8 Relay Status. Bit 0: Alert Bit 1: Action1 Bit 2: Action2 Bit 3: Fire1 Bit 4: Fire2 Bit 5: Minor (if equipped) Bit 6: Urgent/Fault Bit7: Isolate (if equipped) Bits 8-15 unused 9 1 Internal Error Flags – HW Comm U16 Internal Comm Error. For internal use only.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Sensor Status The device’s Sensor Status Structure is READ ONLY with the exception of the Smoke Reference Value and mapped directly to a set of holding registers. The structure in the Firmware is defined as follows: Address Size (16-bit words) Parameter Name Type Description 40031-32 2 System Time U32 Device Time in UNIX seconds epoch format, use Universal Time Stamp instead.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Sensor Status (Cont’d) Address Size (16-bit words) Parameter Name Type Description 52 ½ Ch 3 Air Temperature S8 Real-time sampled air temperature in Channel 3 (multichannel device only) 53 ½ Ch 3 Air Velocity Change S8 Percentage change from baseline air velocity in Channel 3 (multichannel device only) 54-55 2 Ch 3 Air Velocity Baseline F32 Average velocity during baselining in Channel 3 (multichannel de
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Device Logs The device’s Log Structure is READ ONLY and mapped directly to a set of holding registers.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Factory Configuration Address Size (16-bit words) Parameter Name Type Description 40299 ½ SLC Interface Present bool Designates the presence of an SLC interface (ie Eclipse, Flashscan, etc) 300 1 SLC_PROTOCOL_TYPE U16 Defines the supported SLC protocol. CONVENTIONAL 0 CLIP 1 FLASHSCAN 2 ECLIPSE 3 ADVANCED 4 PROTOCOL_OTHER 5 301 1 OEMID_TYPE U16 Defines Device OEM. For internal use only.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Device Configuration Address Size (16-bit words) Parameter Name Type Description 40331 1 Device Config Counter U16 Configuration Counter 332-333 2 Config Timestamp U32 Time of last configuration 334 1 Units U16 Units of Measure for Alarm Threshold Obscuration Values Metric 0 US Standard 1 335 ½ Relays Latching U8 Set latching behavior of minor fault and alarms.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Device Configuration (Cont’d) Address Size (16-bit words) Parameter Name Type Description 372-373 2 ∆ Fire2 Night Threshold F32 Fire2 Alarm Night Obscuration Threshold 374-375 2 ∆ Fire2 Weekend Threshold F32 Fire2 Alarm Weekend Obscuration Threshold 376-377 2 ∆ Alert Acclimate Threshold Max F32 Maximum Alert Alarm Threshold when operating in Acclimate® Mode 378-379 2 ∆ Alert Acclimate Threshold Min F
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Network Configuration Address Size (16-bit words) Parameter Name Type Description 40530 1 Network Config Counter U16 Configuration Counter 531-546 16 Password U8 [32] 547-570 24 E-mail Sender U8 [48] UTF-8 E-mail sender account name string buffer 571-594 24 E-mail Server U8 [48] UTF-8 E-mail outgoing SMTP server name string buffer 595-618 24 E-mail Recipient #1 U8 48] UTF-8 E-mail address of rec
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Appendix A. Configurable options on FAAST A.1. Alarm Configuration Variables Name Description Range Default Value Units AlertThresholdDay The sensitivity where the Alert Alarm will occur during the daytime. 0.00046 – 6.25 0.0015 – 20.5 0.012 0.0396 %/ft %/m Action1ThresholdDay The sensitivity where the Action1 Alarm will occur during the daytime. 0.00046 – 6.25 0.0015 – 20.5 0.05 0.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 A.2. Device Configuration Variables Name Description Range Default Value Acclimate Mode Enable Set to activate acclimate mode operation Enable / Disable Disabled Alert Alarm Latch Set to latch Alert alarm. Requires a RESET to clear alarm. This setting is only valid for conventional product. Latching/Non-Latching Latching Action1 Alarm Latch Set to latch Action1 alarm. Requires a RESET to clear alarm.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1 Technical Support System Sensor strives to provide our customers with outstanding support for the FAAST Fire Alarm Aspiration Sensing Technology® and all our products. For more information, contact us using one of the methods below: Web: E-mail: Phone: systemsensor.com/faast systemsensor.com/contact 800.736.7672 (press 2) Mon-Fri, 7:30 a.m. – 5:00 p.m.