User Manual

TYPE CONDITION RECOMMENDED ACTION
Fault Warning External Monitor Fault signals, but nothing is con-
nected to the external monitor relay.
Attach the 47 K-Ohm resistor, included with FAAST detector, to the External Monitor
terminal when the external monitor function is not being used.
Fault Warning Flow fault signals after power initialization. Check for broken pipe connections or blocked sample holes. Repair any damage to
the pipe network.
Fault Warning Flow fault signals after power initialization. If the FAAST system pipe network has changed or the FAAST detector was moved
to another pipe network, the detector must be re-configured to reset its reference
baseline.
Fault Warning Filter fault signals after power initialization. If the FAAST system pipe network has changed or the FAAST detector was moved
to another pipe network, the detector must be re-configured to reset its reference
baseline. If changes have not been made to the pipe network, replace the filter.
Pipe Network Transport time is significantly longer than the PipeIQ
design indicates.
Set ALERT and ACTION 1 delay to zero.
Pipe Network Transport time is significantly longer than the PipeIQ
design indicates.
Be certain that caps are installed in the two ports not being used.
Pipe Network Transport time is significantly longer than the PipeIQ
design indicates.
Check pipe integrity. Use electrical tape to close all sample holes and check the
pipe for leaks. This can be accomplished by applying 2 psi of compressed air and
measuring with a pressure gauge. The gauge should not drop more than 1 psi in
15 sec.
Pipe Network The pipe network prevents the FAAST device from be
-
ing removed from the mounting bracket.
Loosen pipe mounting brackets enough to allow the pipe to bend and remove the
pipe from the top of the detector.
Pipe Network The pipe network prevents the FAAST device from be
-
ing removed from the mounting bracket.
Cut a ½ inch (13 mm)section of pipe approximately 6 inches (15 cm)above the
detector. Remove the detector and steel plate from the wall. Fit a
5
/
8
(16 mm)inch
spacer behind the steel mounting plate. Permanently connect a union at the loca-
tion where the ½ inch (13 mm) section of pipe was removed. The spacer behind
the back plate will allow the larger diameter union to clear the wall.
PipeIQ The web server isn't refreshing every 10 seconds. If using the Internet Explorer
®
internet browser, go to Tools and select Internet
Options. On the General tab under Temporary Internet Files select Settings. Set the
Check for newer versions of stored pages option to Every visit to the page and click
OK.
PipeIQ Unable to connect to the device. Verify the TCP/IP settings of your network adapter (refer to section PipeIQ FAAST
Connection Troubleshooting for details). Ensure the IP address used to connect
matches the IP address of the FAAST device. The IP address of the device can be
determined by using the IP address blink mode.
PipeIQ Pipes and fittings do not connect on the design page
of PipeIQ.
There are two things to be aware of prior to specifying the next component in the
design. First, orient the view to either FRONT, TOP or RIGHT view. Second, high
-
light the component to be connected such that it shows yellow. Then, add the new
component. Always use one of the three views to move the new component on the
screen.
PipeIQ Cannot edit pipe. Try using one of the three views (FRONT, TOP or RIGHT) to edit.
PipeIQ Cannot disconnect element. Only components with a single connection can be disconnected. In order to discon
-
nect a component from within an assembly, all later components must be discon-
nected first.
Note: Making all component moves/disconnect from a single view will make these
components easier to reassemble.
User Interface Front panel buttons do not work. Buttons may be configured as locked. Follow procedure to unlock buttons or config
-
ure them in the unlock mode.
TABLE 2. TROUBLESHOOTING QUICK GUIDE
SS-400-007 27 E56-3621-003
Maintenance and Troubleshooting