Instruction Manual

D770-17-00 3 I56-0986-008R
NOTE: The sensor assembly is not field replaceable. Do not attempt to disas-
semble these parts. If you have any questions, consult System Sensor. System
Sensor recommends careful consideration of the following factors when speci-
fying and installing Alarm and Supervisory Pressure Switches. Always refer to
the Installation and Maintenance Instruction for specific recommendations on
individual devices before installing the unit.
Electrical ratings stated in literature and on nameplates should not be exceeded.
Overload on switch can cause failure on the first cycle. Always wire
devices according to national and local electrical codes.
Install units away from shock and vibration. Proper electrical fittings should
be used to prevent moisture from entering the enclosure via the conduit.
Test all devices for proper operation after initial installation. Perform pre-
ventive maintenance and periodic testing as required by the applicable
NFPA standards but not less than bimonthly.
Install a back-up control for all critical applications where control failure
could endanger life or property. A backup control to serve as a high or
low limit control is especially recommended for applications where a
runaway condition could result.
Do not mount unit where ambient temperatures will exceed published limits.
Avoid impact or mechanical loading.
Low Pressure
Adjusting
Screw
1/4" Hex Head
(Not Present in
Single Switch
Models)
Each 1/2 turn of Low Pressure adjsuting screw adjusts
pressure approximately 5 psi. Turn counter clockwise to increase
pressure. Turn clockwise to decrease pressure. Each 1/2 turn
of High Pressure adjusting wheel adjusts pressure 11 psi on the
EPS40-2 and 40 psi on the EPS120-2.
NOTE:
Main Adjusting Wheel
(Turn Counterclockwise
to Increase Pressure)
Switch 2
(Low Switch
EPS40-2 and
EPS120-2)
Switch 1
(High Switch
EPS40-2 and
EPS120-2; Low
Switch EPS40-1)
FIGURE 5. ADJUSTMENTS (DUAL-SWITCH MODEL SHOWN):
W0144-02