User Manual
D900-00-00 2 I56-0003-004R
24 Volts 33 Volts
Low Med. High Low Med. High
57 61 52 59 61 64
54 57 60 57 60 62
53 55 58 55 58 60
59 61 64 61 63 66
55 57 60 57 59 62
54 56 59 56 58 61
55 57 61 58 60 63
53 55 58 55 57 60
52 54 57 54 56 59
56 58 62 58 60 64
53 55 58 56 58 62
54 56 60 56 59 61
65 68 70 68 70 74
56 59 62 58 60 64
54 57 60 56 55 61
51 52 58 52 54 60
8 Volts 12 Volts
T
one
Low Med. High Low Med. High
1.2K Repeating 1 Second Chime 51 52 55 53 54 56
1.0K Repeating 1 Second Chime 48 50 54 51 52 54
0.8K Repeating 1 Second Chime 47 47 53 49 51 52
1.2K Repeating 1/4 Second Chime 53 54 58 55 57 59
1.0K Repeating 1/4 Second Chime 49 50 54 51 53 54
0.8K Repeating 1/4 Second Chime 48 50 53 50 52 53
1.2K Temporal 3 Chime 51 52 56 52 54 55
1.0K Temporal 3 Chime 48 49 54 49 51 51
0.8K Temporal 3 Chime 46 47 51 48 50 51
1.2K Single Stroke Chime 52 53 58 52 54 56
1.0K Single Stroke Chime 47 48 53 50 51 59
0.8K Single Stroke Chime 47 48 53 49 50 52
3.0K Continuous Electromechanical 56 57 61 59 60 67
3.0K Temporal Electromechanical 51 52 56 53 54 61
0.5K Continuous Electromechanical 48 49 53 51 52 56
0.5K Temporal Electromechanical 45 47 51 47 49 53
SpectrAlert Electronic Chime Sound Output Guide
SpectrAlert Electronic Chime Current Draw*
12VDC: 18–31mA
24VDC: 31–61mA
*Average current draw varies with tones selected. Current ratings per
System Sensor testing at 12VDC and 24VDC.
SpectrAlert Chime Switch Settings
SpectrAlert Chime Tones
Repeating 1-Second Chime
Repeating
1
/4-Second Chime
Temporal 3 Chime
Single Stroke Chime
Continuous 500Hz Electromechanical and 3kHz Electromechanical
Temporal 500Hz Electromechanical and 3kHz Electromechanical
Scale:
1 second
Switch 1=on 0=off
1
2 3
4
Hz
Type
1 1 1 1 1.2k Repeating 1-second chime
1 0 1 1 1.0k Repeating 1-second chime
1
1 0
1
0.8k
Repeating 1-second chime
1
0 0
1
1.2k
Repeating
1
/
4
-second chime
1 1 1 0 1.0k Repeating
1
/4-second chime
1
0 1
0
0.8k
Repeating
1
/
4
-second chime
1 1 0 0 1.2k Temporal 3 chime
1
0 0
0
1.0k
Temporal 3 chime
0
1 1
1
0.8k
Temporal 3 chime
0 0 1 1 1.2k Single Stroke Chime
0 1 0 1 1.0k Single Stroke Chime
0 0 0 1 0.8k Single Stroke Chime
0
1 1
0
3.0k
Electromechanical Continuous
0
0 1
0
3.0k
Electromechanical Temporal 3
0 1 0 0 0.5k Electromechanical Continuous
0 0 0 0 0.5K Electromechanical Temporal 3
VOLUME
SWITCH
5 6
0 0 LOW
1 0 MED
1 1 HIGH
NOTE: Factory default setting is 1.0K Repeating 1 Second Chime set at High volume.
All chime models were only tested at the 8-17.5 and 16-33 Volt-FWR/DC limits. This does not include the 80% low-end or 110% high-end
voltage limits.