User Manual

SS-400-007 4 I56-3620-005
ASP18-02
TABLE 1. TERMINAL DESIGNATIONS
NUMBER NAME TERMINAL BLOCK
T1 External Power -
1
T2 External Power -
T3 External Power +
T4 External Power +
T5 N/A
2
T6 N/A
T7 N/A
T8 N/A
T9 Alert NO
3
T10 Alert COM
T11 Alert NC
T12 Action 1 NO
4
T13 Action 1 COM
T14 Action 1 NC
T15 Action 2 NO
5
T16 Action 2 COM
T17 Action 2 NC
T18 Fire 1 NO
6
T19 Fire 1 COM
T20 Fire 1 NC
T21 Fire 2 NO
7
T22 Fire 2 COM
T23 Fire 2 NC
T24 Minor Fault NO
8
T25 Minor Fault COM
T26 Minor Fault NC
T27 Urgent Fault NC
9
T28 Urgent Fault COM
T29 Urgent Fault NO
T30 Isolate NO
10
T31 Isolate COM
T32 Isolate NC
T33 Ext Monitor/Reset -
11
T34 Ext Monitor/Reset -
T35 Ext Monitor/Reset +
CABLING REQUIREMENTS
The FAAST system provides a series of Euro style pluggable terminals, located
behind the left side door of the unit.
Refer to Table 1 for the proper electrical connections to the unit. Refer to Table
2 for a typical connection for monitoring the FAAST system at a Fire Alarm
Control Panel (FACP).
SYSTEM POWERING
The following procedure describes how to initially power up the FAAST system.
1. Unplug the unit’s power connector to the unit before turning ON the
power.
2. Turn on the power.
3. Check the voltage at the connector. Make sure it is within the required
voltage range.
4. If the voltage is within the proper range, reconnect the power connector
to the unit.
5. Verify the system fan starts up and air begins to flow out of the exhaust port.
6. Connect a computer, with the PipeIQ software installed, to the unit using
the Ethernet connection on the bottom of the unit.
7. Use the PipeIQ software to set up the unit configuration required for the
particular application.
8. When the configuration is complete, remove the Ethernet connection to
the unit.
USER INTERFACE
The user interface, shown in Figure 4, provides the following information:
Detector Status: Normal, Alarm, Fault or Isolate
Alarm Level; Alert, Action 1, Action 2, Fire 1 and Fire 2
Particulate Levels; 1-10 relative to Alert
Fault Status
Flow Level
Test, Reset and Isolate Buttons
TABLE 2. FACP WIRING DIAGRAM
N.C.
N.O.
C.
Fire2 Relay
Contacts
(T7)
Fire Panel (FACP) typical connection
FAAST 8100
Fire Alarm Aspiration Sensing Technology
®
FAAST 8100
Fire Alarm Aspiration Sensing Technology®
for monitoring of device
Alarm
Short = Fire
Open = Fault
EOL
N.C.
N.O.
C.
Fire1 Relay
Contacts
(T6)
Alarm
Short = Fire
Open = Fault
N.C.
N.O.
C.
Action2
Relay
Contacts
(T5)
Alarm
Short = Fire
Open = Fault
N.C.
N.O.
C.
Action1
Relay
Contacts
(T4)
Alarm
Short = Fire
Open = Fault
N.C.
N.O.
C.
Alert Relay
Contacts
(T3)
Alarm
Short = Fire
Open = Fault
N.C.
N.O.
C.
Isolate Relay
Contacts
(T10)
Supervisory
Short = Isolate
Open = Fault
N.C.
N.O.
C.
Urgent Relay
Contacts
(T9)
Short = Urgent Fault
Open = Fault
N.C.
N.O.
C.
Minor Relay
Contacts
(T8)
Short = Minor Fault
Open = Fault
N.C.
N.O.
C. (Reset)
Panel
Remote
Reset
-
-
+
Monitor
Short =
Reset
Open = Fault
FACP
Supervisory
Supervisory
EOL
EOL
EOL
EOL
EOL
EOL
EOL
EOL
47K