Owner manual
D400-01-01  3  I56-0278-008R
Figure 2:Maintenance
It  is  recommended that  the  detector  be  removed  from its 
mounting base to facilitate easier cleaning. The detector is 
cleaned as follows:
NOTE: Before removing the detector, notify the proper 
authorities  that  the  smoke  detector  system  is  undergoing 
maintenance,  and  will temporarily be  out of  service. Dis-
able  the  zone  or  system  undergoing  maintenance  to  pre-
vent unwanted alarms.
1.  Remove the detector screen and cover assembly by de
-
pressing the three lock prongs on the top of the cover, 
rotating the cover counterclockwise, and  pulling the 
screen and cover assembly away from the detector. (See 
Figure 2.)  Usage  of  a  System  Sensor  CRT400  cover re-
moval tool is recommended.
2. Remove the screen from the cover.
3.  Use a vacuum cleaner to remove dust from the screen, 
the cover, and the sensing chamber.
4.  After cleaning, snap the screen into the cover, then place 
the cover and screen assembly on the detector, turning 
clockwise until it is locked in place.
5. Reinstall the detector.
6. Test the detector as described under TESTING.
7. Notify the proper authorities that the system is back on line.
LOCK PRONG
REMOVABLE SCREEN
(P/N RS14)
REMOVABLE 
COVER
FOR
CLEANING 
SENSING CHAMBER
S0138-00