User guide
D400-08-00  2   I56-280-05R
Mounting
Each 1412 and 1424 detector is supplied with a mounting 
bracket kit that permits the detector to be mounted:
1. Directly to a 3
1
⁄2 inch or 4 inch octagonal, 1
1
⁄2 inch deep 
electrical box, or
2. To a 4 inch square electrical box by using a plaster ring 
with the supplied mounting bracket kit.
Spacing
Spacing  of  30  ft.  on  a  smooth  ceiling  as  per  NFPA  72E. 
Where  conditions or response requirements vary, other 
spacing may apply.
Wiring Installation Guidelines
All wiring must be installed in compliance with the National 
Electrical Code and the applicable local codes, and any spe-
cial requirements of the local authority having jurisdiction. 
Proper wire gauges should  be used.  The conductors used 
to connect smoke detectors to control panels and accessory 
devices should be color-coded to prevent wiring mistakes. 
Improper connections can prevent a system from respond-
ing properly in the event of a fire.
NOTE:  Refer  to  releasing  device  manufacturer’s  installa-
tion instruction for proper connections.
NOTE: Contacts are shown in stand-by mode  and will 
transfer in alarm condition.
CAUTION
For system supervision: for terminals 1, 2, 7, and 8, do not 
use looped wire under terminals. Break wire run to provide 
system supervision of connections.
For  signal  wiring  (the  wiring  between  interconnected 
detectors), it is recommended that the wire be no smaller 
than  18  gauge.  Wire  sizes  up  to  12  gauge  wire  may  be 
used. For best system performance, the power (+) and (–) 
loop wires should be twisted pair and installed in separate 
grounded conduit to protect the loop from extraneous elec-
trical interference.
Smoke  detectors  and alarm  system  control  panels have 
specifications  for allowable  loop  resistance.  Consult the 
control  panel  manufacturer’s  specifications  for the  total 
loop  resistance  allowed  for  the  particular  model  control 
panel being used before wiring the detector loops.
TAMPER
RESISTANT
TAB
TO
 MAKE DETECTOR TAMPER RESISTANT,
BREAK OFF TAB EXTENSION
AT
 SCRIBED LINE
Figure 1. Flush mounting of detector on 4 inch 
octagonal box:
Figure 2. Detector mounting bracket:
S0139-00
S0140-00
COMMON
N/O
N/C
AUXILIARY
CONTACTS
FORM C
4
5
6
7
8
2
1
+
-
POWER
ALARM
CONTACTS
FORM A
N/O
A78-1811-00
S0165-00
Figure 3. Wiring diagram for models 1412 and 1424 detectors used with Class A or 
Class B four-wire control panels.




