Instructions / Assembly
®
System 1738 Installation Methods 3
Product Application
(a)  System 1738 PVC Gas Venting System is intended for 
venting of Categories II and IV gas fired appliances
(b)  System 1738 PVC Venting System is suitable for a 
maximum flue gas temperature of 149
o
F (65
o
C)
(c)  System 1738 PVC has a zero clearance to 
combustible construction
(d)  Some custom System 1738
®
 PVC fittings, fitting 
assemblies and terminations manufactured for the 
USA market are dual certified to both UL 1738 for 
USA and ULC S636 for Canada. These components 
are black in color and are identified with a UL 1738 
and a ULC S636 marking on the certification 
sticker found on the component. For installation 
requirements of these components in Canada, 
please reference the System 636
®
 Installation 
Manual at ipexna.com/Canada.
Limits of Use and Application
(a)  The vent sizing and maximum vent length of plastic 
piping for Categories II and IV appliances shall be 
accordance with the appliance manufacturer’s 
instructions.
(b)  All System 1738 gas venting pipe and fittings must 
be carefully inspected by qualified personnel before 
use to ensure no damage has occurred during 
transportation. Any damaged product must be 
replaced. No attempt at repairs are to be made at 
the job site.
(c)  The common temperature changes in a gas venting 
application will cause the system to expand and 
contract accordingly. Proper care must be taken 
to allow for this movement through walls, ceilings, 
and roof penetrations. The venting system must be 
supported in accordance with these instructions.
Follow IPEX solvent welding procedures as shown in 
this guide, and check for proper joint construction 
when joining pipe to fittings.
NOTICE
As per UL 1738 standard, DO NOT mix pipe, fittings or 
joining methods from different Manufacturers as they 
have different joint systems and adhesives. This can 
result in unsafe conditions and will void certification 
and warranty.
Improper installation of System 1738 PVC systems may 
result in personal injury or death. Only qualified personnel 
should attempt the installation of gas burning equipment 
and vent, following the gas appliance and vent  
manufacturers directions.
 WARNING
(d)  Only certified System 1738 PVC primer and cement 
shall be used to assemble System 1738 PVC venting 
systems. 
(e)  Venting should be as direct as possible with a 
minimum number of fittings. The maximum vertical 
rise or horizontal run of vent pipe plus the effective 
length of all fittings in a single vent installation shall 
not exceed the maximum vent length requirements 
outlined in the appliance manufacturer’s installation 
instructions.
(f)  All framing requirements for floor and ceiling 
penetrations shall be in accordance with the local 
building code and/or the local regulatory authority. 
(g)  All penetrations of fire rated floors and walls shall be 
firestopped as described in he Firestop section of 
this guide.
(h)  Roof penetrations should be sealed with a plumbing 
roof boot or equivalent flashing as per the local 
building code, or as permitted by the local regulatory 
authority. Chemical attack can cause product 
failure. Only use PVC chemically compatible sealants, 
gaskets and adhesives.
(i)  If spray foam insulation comes in contact with System 
1738, it is recommended that foam be applied in a 
maximum layer thickness of 2 inches (50mm) until the 
required thickness of insulation is achieved.
(j)  All horizontal sections of the venting system must 
be installed with a slope not less than 0.25 in./
ft. down towards the appliance in order to collect 
condensate and remove condensate generated 
inside the line. The removal of condensate will help 
reduce the possibility of ice buildup and blockage. 
Refer to the appliance manufacturers’ installation 
instructions for further details regarding the 
installation of necessary condensate drains.
NEVER use compressed air or gas in  
System 1738 pipe and fittings
NEVER test PVC pipe and fittings with 
compressed air or gas, or air-over-water 
boosters.
Use of compressed air or gas in System 1738 pipe 
and fittings can result in explosive failures and cause 
severe injury or death.
 WARNING
System 1738
®
 PVC Categories II and IV Gas Venting System is third party certified to UL 1738, latest edition. The following 
installation methods have been prepared in conformity with the requirements of section 47 of UL Standard 1738.










