Instructions / Assembly
®
System1738 Installation Methods 27
Air Intake
Distance above avg. snow fall or grade
Ref: local code requirements. Maintain 
12" clearance above highest 
anticipated snow level or grade 
whichever is greater.
Exterior wall
System1738
Round Face Plate
1" Min, 2" Max
(From wall
or Face Plate)
Clamp or Strap
(Field Supplied)
Exhaust
Air Intake
Exhaust
12" Min
Clearance to Soffit
Figure 19: Typical Concentric Vent Side Wall Termination
Concentric Vent Kit Assembly
1.  Once the installer has determined the termination 
location, cut a hole in the roof or wall 1/2" larger 
than the “C” dimension referenced in Table 5 for 
the part being installed. The size of the hole can 
vary greatly depending on the roof pitch.
2.  As per the procedures outlined in this guide, solvent 
weld the inner pipe to the concentric wye fitting.
3.  Solvent weld the outer pipe to the concentric wye 
fitting. 
4.  Slide the assembly through the roof or wall 
penetration. (Install flashing if needed).
5.  The outer pipe shall be only a friction fit with the 
cap. To permanently affix the rain cap, apply 
solvent cement to the inner pipe as per the 
procedures outlined in this guide. For installations 
where removal of the cap may be required for 
service of the termination or cleaning the cap, it can 
be fastened mechanically (drill location reference 5  
in Figure 18). 
6.  Once the rain cap is installed, and the kit secured as 
outlined below in Figure 18, the kit can be connected 
to the venting system.