Instructions / Assembly
®
System 1738 Installation Methods 21
Accessory Installation Instructions
Access Tee
1.  The access tee shall be 
installed on a vertical run 
of pipe to prevent the 
collection of condensate.
2.  PVC Access Tees shall 
only be used on System 
1738 PVC venting systems. 
Do not mix pipe, fittings, 
cements, or joining 
methods from different 
Vent manufacturers. 
This can result in unsafe 
conditions and will void 
the certification and 
warranty.
3.  Solvent cement the access tee into the piping 
system as per the Solvent Welding Guidelines 
instructions specified in this guide. Allow for the 
proper cure times referenced in this guide before 
proceeding to next step.
4.  Apply two full turns of Teflon
®
 Tape to the threaded 
portion of the 1/2" plug.
5.  Hand thread and hand tighten the plug into the 
bushing. Take care not to cross thread the fittings.
6.  Once hand tight, slowly turn the plug an additional 
one and a half (1.5) turns.
7.  If the fittings appear to be damaged during 
threading, the entire assembly should be replaced. 
If the Teflon
®
 Tape was unraveled during threading, 
the plug will need to be re-installed with new tape. 
8.  Repeat steps 4-7 every time the plug is removed 
ensuring to use new Teflon
®
 Tape each time.
Refer to the appliance manufacturer’s installation 
instructions to ensure that the low profile side wall 
termination kit is permitted for use. The IPEX Low Profile 
side wall termination kit is fully certified for use with IPEX 
System 1738 product only.
System 1738 PVC Low 
Profile vent kits are made 
from a UL1738 certified PVC 
compound and are rated 
to a maximum temperature 
of 149
o
F.
The vent termination must 
maintain all termination 
clearances and be installed in accordance with local 
building code and NFPA 54 / ANSI Z223.1 National Fuel 
Gas Code. (see Figure 13)
Item #
Flush Mount Vent Kit 
Size (inches)
Pipe O.D. 
Hole Spacing  
(ctr to ctr)
397984 2 2.375" 5.6"
397985 3 3.5" 5.6"
397986 4 4.5" 5.6"
TABLE 4 – Low Profile Termination Kits Dimensions
TABLE 3 – Each Kit Contains:
Qty Item Description
1 Base (two holes) 
1 Cap (one hole)
8 Stainless Steel Screws
4 Plastic Anchors
Low Profile Side Wall Termination Kit
Installation Procedure
1.  When locating the penetration of the vent and air 
pipe, ensure the termination is properly oriented 
as shown in Figure 14 and ensure that it maintains 
minimum clearance requirements as shown in Figure 13. 
For multiple vent terminations, ensure that a minimum 
clearance of 12 inches is maintained between edge 
of air inlet and adjacent vent outlet and that all vent 
pipes and air inlets terminate at the same height to 
avoid the recirculation of flue gases and the possibility 
of causing severe personal injury, death, or substantial 
property damage. (see Figure 16)
2.  When installing the vent termination in a vertical 
configuration, ensure the vent piping is located above 
the air inlet piping. This will avoid the risk of flue gas 
products recirculating into the air inlet and building. 
(see Figure 14).
Refer to Figure 15 for side wall termination assembly