User's Manual

Subfloor EZ Node Hardware Installation Guide
Version 1.0
15
Validating and Commissioning the Subfloor EZ Node
Installation
Validate and commission the Subfloor EZ Node installation by activating the Subfloor EZ Node and
confirming node communication with the SynapSense Web Console software application. Refer to the
Web Console User Guide for detailed information.
Before beginning the following steps, first verify (with lead supervisor or installer) all necessary
installation activities, including software installation and file exports, are completed. Assure all
peripheral hardware and software is powered on and functional (gateway, server, etc.).
1. Confirm sensor node operations and communications. Refer to the Web Console User Guide for
detailed information.
a. Open Web Console and select the data center from the Sites list.
b. Click the Data View tab.
c. Select Pressure from the Data View drop-down menu. A tabular view of the Cabinet Node
data displays.
2. Verify green checkmarks display for each installed object in the Status column.
3. If a red X displays for an object in the Pressure column, check for loose connections, obstructed
diffusers, and reversed hose connections. Correct the errors and repeat the previous steps for
software communication validation.
4. If there are no loose connections, obstructions, or reversed hose connections, reset the node by
turning it off (press the light pipe dimple once) and on (press the light pipe dimple once again).
Allow time for the module to connect to the network and repeat the previous steps for software
communication validation.