Specification Sheet

TempControl
®
Location:
Specification
TempControl thermostatic mixing valve made from lead
free** metal components. Features serviceable integral
check stops (see table 1 for ow rates).
Temperature control range:
70°F - 150°F (21.1°C - 65.6°C)
Approach temperature:
5°F (-15°C)
**According to US Senate bill S.3874, the term “lead free” is dened
as follows: “not more than a weighted average of 0.25 percent lead
when used with respect to the wetted surfaces of pipes, pipe ttings,
plumbing ttings, and xtures”
Modifications
Warranty
Limited Lifetime - to the original end purchaser in
consumer/residential installations.
5 Years - for industrial/commercial installations.
Refer to www.symmons.com/warranty for complete
warranty information.
Note: Append appropriate -sufx to model number.
-NI
Rough nickel nish
-P
Polished chrome highlight nish
-W
Wall mounting bracket
Compliance
-ASME A112.18.3/CSA B125.3-12
-ASSE 1017
-NSF/ANSI 61.9, NSF/ANSI 372
7-700
Thermostatic Mixing Valve
Specification Submittal
Coordinating Model Numbers
T-425-700
3" bimetal dial thermometer
BV-700/900
Volume control shut-off valve
SV-700
Solenoid valve
TF-700
Tee tting
WHA-1
Water hammer arrestor
TABLE 1: FLOW RATE - gpm (L/min)
VALVE
MODEL
MIN. FLOW
RATE*
MIN. FLOW
RATE
PRESSURE DIFFERENTIAL - psi (kPa)
5 psi
(34 kPa)
10 psi
(69 kPa)
20 psi
(138 kPa)
25 psi
(172 kPa)
30 psi
(207 kPa)
45 psi
(310 kPa)
7-700
0.5 gpm
(1.9 L/min)
13 gpm
(49 L/min)
25 gpm
(95 L/min)
43 gpm
(163 L/min)
57 gpm
(216 L/min)
62 gpm
(235 L/min)
66 gpm
(250 L/min)
77 gpm
(292 L/min)
*Minimum ow rate when valve is installed at or near the hot water source with recirculated tempered water and
continuously operating circulating pump.
Flow Rate Chart

Summary of content (2 pages)