Specification Sheet

1
TempControl 7 Series
Specification Submittal
7-400
Coordinating Model Numbers Specification
Configurations
Note:
Symmons Industries, Inc. 31 Brooks Drive Braintree, MA 02184 (800)796-6667 Fax: (800)961-9621
©2013 Symmons Industries, Inc.
www.symmons.com
gethelp@symmons.com
ZV-1147 REVC 11/07/13
HTA-100
BV-400
High temp audio/visual alarm system
Volume control shut off valve
T-425-400
3” bimetal dial thermometer
SV-400
WHA-1
Solenoid valve
Water hammer arrestor
TF-400
Tee fitting
Valve and piping assembly
Valve and piping in cabinet with cold
water bypass
Valve and piping in cabinet
A
BW
B
Location:
Table 1: Flow Rate - gpm (L/min)
Valve Model Min. Flow Rate* Min. Flow Rate
Pressure Differential - psi (kPa)
5 psi
(34 kPa)
10 psi
(69 kPa)
20 psi
(138 kPa)
25 psi
(172 kPa)
30 psi
(207 kPa)
45 psi
(310 kPa)
7-400
0.5 gpm
(1.9 L/min)
9 gpm
(34 L/min)
18 gpm
(68 L/min)
27 gpm
(102 L/min)
37 gpm
(140 L/min)
41 gpm
(155 L/min)
44 gpm
(167 L/min)
53 gpm
(201 L/min)
Warranty
5 Years - for commercial installations.
Refer to www.symmons.com/warranty for complete
warranty information.
Compliance
-ASME A112.18.1/CSA B125.1
-CSA B125.3
-ASSE 1017
-CA 116875 (AB 1953)
-NSF 372
-US S.3874
TempControl thermostatic mixing valve made from lead
free** metal components. Features serviceable integral
follows: “not more than a weighted average of 0.25 percent lead when
Approach temperature: 5°F (-15°C)
Temperature control range:
70°F - 150°F (21.1°C - 65.6°C)
operating circulating pump.

Summary of content (2 pages)