T12 SYSTEMS
Input Input System
Current Rated Ballast Power Efficacy
2
Item (AMPS) Lamp
1
Lumens No. of Factor System (W) (Im/W)
Number Description
@120/277V Type (lm) Lamps (BF) Lumens @120/277V @120/277V BEF
1
75304 QTP2x40T12/UNV/RS/SC 0.56/0.24 F40T12/D30/ECO 3200 2 0.91 5630 67/67 76 1.36
0.45/0.20 F34/D830/SS 2900 2 0.91 4930 54/54 78 1.69
0.29/0.13 F40T12/D30/ECO 3200 1 0.91 2815 35/35 80 2.60
0.24/0.11 F34/D830/SS 2900 1 0.91 2465 28/28 88 3.21
75305 QTP2x96/T12/UNV/IS 1.13/0.48 F96T12/D41/ECO 6420 2 0.88 11,040 135/132 82/84 0.65
0.90/0.39 F96T12/CW/SS 5300 2 0.87 9220 108/106 85/87 0.81
0.91/0.40 F72T12/CW 4500 2 0.92 8280 108/107 77/77 0.85
0.55/0.25 F96T12/D41/ECO 6420 1 1.04 6485 84/82 77/79 1.24
0.53/0.24 F96T12/CW/SS 5300 1 1.04 5830 70/68 83/86 1.49
0.70/0.31 F72T12/CW 4500 1 1.05 4815 68/67 70/72 1.54
1
Ballast Efficiency Factor (BEF) shown = (Ballast Factor x 100) divided by Input Power (Note: calculation based on lowest wattage value).
2
System Efficacy calculation based on lowest input power value unless otherwise noted.
75304 replaces 50314
75305 replaces 50308
Also compatible with other manufacturer’s equivalent lamp types that meet ANSI standards.
Starting Method:
RS - Rapid Start
IS - Instant Start
Circuit Type: RS - Parallel
IS - Parallel
Starting Temp: 5 0°F (10°C)
SUPERSAVER
®
Lamps: 60°F(16°C)
Input Frequency: 60 Hz
THD: QTP40T12/UNV RS: <10%;
QTP2x96T12 IS: <15%
Power Factor:
QTP40T12/UNV RS:>97%
QTP2x96T12 IS >0.96 (for F96T12);
>0.91(for other lamps)
Input Voltage: ±10% of Rated Input
Lamp Crest Factor: <1.6
Lamp Frequency: >20 kHz
UL Listed Class P, Type 1 Outdoor
CSA or CUL Certified
70°C Max. Case Temp.
FCC 47CFR Part 18 Non-Consumer
Class A Sound Rating
ANSI C62.41 Cat A. Transient Protection
Specifications
Data based on F40T12 for RS, F96T12 for IS
Item Number 75304 QTP 2 x 40T12 / UNV / RS SC
QUICKTRONIC PROFESSIONAL
Number of Lamps (2)
Case Size
Starting Type / Ballast Factor
Line Voltage (120-277V)
Primary Lamp Wattage
System Life / Warranty
QUICKTRONIC products are covered by the
QUICK 60+
®
warranty. For additional details,
refer to the QUICK 60+ warranty bulletin.
Normal Ballast Factor
T12
Professional Series
Dimensions:
Model QTP2x40T12/UNV/RS/SC enclosure size
Overall: 9.5" L x 1.3" W x 1.0" H
Mounting: 8.9"
Weight: 1.25 lbs ea. (approx.)
Dimensions:
Model QTP2x96/T12/UNV/IS enclosure size
Overall: 9.5" L x 1.3" W x 1.0" H
Mounting: 8.9"
Weight: 4.67 lbs ea. (approx.)
QTP2X96/T12/UNV/IS
LAMP
LAMP
Blue
Blue
Red
Black
White
LAMP
Blue
Blue
Red
Black
White
Line
Line
BALLAST
BALLAST
Cap off/Insulate unused leads for 1000V.
Ground Ballast and mount lamps within 1/2" of grounded metal reflector
QTP 2x96T12 IS
Note: For one lamp application, cap blue lead. Insulate to 1000 volts.
Performance Guide
QTP 2x40T12 RS
QTP2X40T12/UNV/RS/SC
BALLAST
LAMP
White
BlackLine
Yellow
Yellow
Blue
Blue
Red
Red
LAMP
BALLAST
White
BlackLine
Ground Ballast and mount lamps within 1/2" of grounded metal reflector
Yellow
Yellow
Blue
Blue
Red
Red
LAMP
Cap off/Insulate unused leads for 600V.
LAMP
LAMP
LAMP
BALLAST
Blue
Blue
Blue
Red
Black
White
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 3x32
BALLAST
LAMP
Black
White
Blue
Red
QUICKTRONIC 1x32
BALLAST
LAMP
LAMP
LAMP
LAMP
Black
White
Yellow
Yellow
Blue
Blue
Red
Red
Note: For three lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC 4x32
QUICKTRONIC 1x40DL
BALLAST
Black
White
Blue
Red
BALLAST
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 2x40DL
Black
White
Blue
Blue
Red
Note: For one lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC 2x59*
QUICKTRONIC 2x96IS
BALLAST
Black
White
Blue
Blue
Red
LAMP
LAMP
QUICKTRONIC 2x96HO
Black
Line
White
Yellow
Yellow
Blue
Blue
Red
Red
BALLAST
LAMP
LAMP
QUICKTRONIC 1x96HO
Black
Line
White
Yellow
Yellow
Blue
Blue
Red
Red
BALLAST
LAMP
LAMP
LAMP
Blue
Blue
Red
BALLAST
Black
White
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 2x32
BALLAST
QUICKTRONIC FM (1 LAMP)
Note: For QT-FM green ground wire to terminal required.
LAMP
Black
White
Blue
Red
QUICKTRONIC 3x40DL
BALLAST
Black
White
Blue
Blue
Blue
Red
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC FM (2 LAMP)
Note: For QT-FM green ground wire to terminal required.
LAMP
LAMP
Blue
Yellow
Red
BALLAST
Green
Black
Green
White
Note: For one lamp application,
individually cap each yellow lead. Insulate to 600 volts.
Ground Ballast and mount lamps within 1/2" of grounded metal reflector
Ground Ballast and mount lamps within 1/2" of grounded metal reflector
Products distributed by
LEDVANCE LLC
For Customer Service contact
1-800-LIGHTBULB
SYLVANIA, QUICK 60+, QUICKSENSE, PROStart, POWERSENSE, and
QUICKSTEP are registered trademarks of OSRAM SYLVANIA Inc. QUICK
7XL and QUICK 7XL+ are trademarks of OSRAM SYLVANIA Inc. OSRAM
and QUICKTRONIC are registered trademarks of OSRAM GmbH.
OCTRON, SUPERSAVER, XP, XPS, PENTRON, and ECOLOGIC are
registered trademarks of LEDVANCE LLC. DULUX is a registered
trademark of LEDVANCE GmbH.
All other trademarks are those of their respective owners.
Specifications subject to change without notice.
© 2018 OSRAM SYLVANIA Inc. All rights reserved.
QUICKTRONIC
®
T12
Electronic Fluorescent Ballasts
40T12RS & 96T12IS Universal Voltage (120-277V)
QTP2X96/T12/UNV/IS
LAMP
LAMP
Blue
Blue
Red
Black
White
LAMP
Blue
Blue
Red
Black
White
Line
Line
BALLAST
BALLAST
Cap off/Insulate unused leads for 1000V.
Ground Ballast and mount lamps within 1/2" of grounded metal reflector