Programming Instructions

Programming screen « INSTALLATION » Page 41/74
Basic load OFF %
- Enter the base load value. Here it’s disabled, current value is (OFF).
Press to open the numeric keyboard and enter the desired value.
This setting is only available if the unlock option is enabled in the setting options.
Be careful, the basic load is a permanent dosage power regardless of the dosage need. This
function is to be used with great care to avoid overdosage.
Maximum time OFF min
- Enter the maximum dosage time value. Here it’s disabled, current value is (OFF).
Press to open the numeric keyboard and enter the desired value.
Activation threshold 90 %
- Enter the dosage power from which the dosage time is counted. Here it’s set automatically according
to the dosage mode at (
90). Press to open the numeric keyboard and enter the desired value.
This setting is only available if the unlock option is enabled in the setting options.
Save:
- When a change is made, the “SAVE” button appears (floppy icon), you must save your configuration
by pressing it.
b) Dosage mode – Threshold [1221]
Press to open following screen.
Dosage need
parameter
90
No counting of dosing time Reset time to zero
Couting of dosing time
pH
Setpoint & dosage settings
E01 pH PI1
High threshold
Low threshold
M
aximum
time
Mode Threshold
Basic load
Active threshold
7,2
0
7,
0
0