Programming Instructions
Programming screen « INSTALLATION » Page 30/74
Relay delay time - Run (ON) : 2 second(s)
- Enter the wait time value before the alarm is taken into account. Here the value is (2).
Press to open the numeric keyboard and enter the desired value.
Possible adjustment from 0 to 240 second(s).
Relay delay time - Stop (OFF): 2 second(s)
- Enter the wait time value before the disappearance of the alarm is taken into account. Here the value
is (
2).
Press to open the numeric keyboard and enter the desired value.
Possible adjustment from 0 to 240 second(s).
Relay state duration for pulse mode - Active (ON):
0 second(s)
- Enter the time value during which the relay will be active in the alarm time slot. Here the value is (0).
Press to open the numeric keyboard and enter the desired value.
Possible adjustment from
0 to 240 second(s).
Relay state duration for pulse mode – Inactive (OFF):
0 second(s)
- Enter the time value during which the relay will be inactive in the alarm time slot. Here the value is
(
0).
Press to open the numeric keyboard and enter the desired value.
Possible adjustment from 0 to 240 second(s).
Pulse mode time:
This setting allows pulses to be generated throughout the duration of the alarm. For example, if
the two values entered are 1 second, the relay will open 1 second and close 1 second repeatedly
throughout the alarm.
To delete a relay output:
You must select « NO » in the relay function and save your configuration by pressing the “SAVE”
button.
e) Relay outputs in State mode [1531]
Example with creation of a relay in State mode.
Press to open the following screen.
PO2 Function State
- Output relay operation mode selection, on this selection button we find the information of the output
being modified (
PO2) and the function currently selected (State).
Press to change it.
Assignment Water circulation DI1
- Selection of the contact to which this relay is attached, on this selection button we find the
information of the type of contact (
Water circulation) and its « code » (DI1).
Press to change it.
For all other parameters:
- See relay configuration in alarm mode.
Not used
Setting output relay
PO2 Function
State
Assignment Water circulation DI1