Programming Instructions

Programming screen « INSTALLATION » Page 18/74
Special case of a pulse flowrate
DI1 Function Flowrate
- Digital input operation mode selection, on this selection button we find the information of the input in
the process of modification (
DI1) and the currently selected function (Flowrate). Press to change it.
Unit l/h
- Select flowrate unit, selection button displays the information of the currently selected unit (l/h).
Press to change it.
Flowrate min. 0 l/h
- Information on the low value of the flowmeter. This part is grayed out (not accessible), it’s frozen at
(
0).
Flowrate max. 100,00 l/h
- Enter the high value of the flowrate. Here the current value is (100.00).
Press to open the numeric keyboard and enter the desired value.
Unit imp/l
- Pulse unit selection, on this selection button you will find the information of the currently selected unit
(
imp/l). Press to change it.
Volume per pulse ratio 1,0000 imp/l
- Enter the pulse weight for flow calculation. Here the current value is (1,0000).
This value is directly related to your flowrate and installation, to calculate it, you must refer to the
flowrate documentation.
Press to open the numeric keyboard and enter the desired value.
To delete an input contact:
- You must select « NO » from the list of functions and save your configuration by pressing the “SAVE”
button.
Setting digital input
DI1
Function
Flowrate
Unit l/h
Volume per pulse ratio
Imp/l
1,000
Flowrate min. 0 l/h
Flowrate max. 100,00 l/h
Unit imp/l
1.0000