Programming Instructions
Programming screen « INSTALLATION » Page 14/74
Active the advanced configuration of the 4…20mA outputs
- This option, if checked, gives access to the « special » current settings. It’s then possible to define
the current generated in two special cases:
o In dosage mode:
Fault current
Over range current
o In transfer mode:
Inhibition current
Fault current
Over range current
Let the choice of Insulated / Non-insulated sensors
- This option, if checked, gives you the complete choice on the inputs sensors from AI1 to AI4.
AI3 & AI4 are inputs 4…20mA NOT Isolated, if the above option is checked, make sure that the sensor
you select for these inputs is an isolated sensor.
2) Menu « Configuration & Installation » - « INPUTS » [0231]
« INPUTS » menu will allow you to access the configuration of the sensors that will be connected on
the inputs (Potentiometric, Analog 4…20mA or Digital)
Press to open the following screen.
Screen presents inputs that are already configured and those that are not used. By pressing an already
configured entry, you can change its configuration, or pressing an unused entry, configure its installation.
Entry already configured.
Press to edit its configuration.
Entry unused.
Press to configure its installation.
Option not accessible.
INPUTS
Setting inputs
Inputs
Digitals
PI1
pH
Potentiometric inputs
Analog inputs
Insulated
Not insulated
Additional module
AI1
Free chlorine
DI1
Water circulation
PI2
Not used
AI2
Not used
DI2
Not used
DI3
Not used
DI4
Not used
AI3
Temperature
AI4
Not used