Programming Instructions
Programming screen « INSTALLATION » Page 13/74
Lock code « Installation »
- Activate or deactivate the security code to access the « Installation » menu
Lock code « Settings »
- Activate or deactivate the security code to access the « Settings » menu
Lock the « Settings » level with the installer code
- Use the « Installer » code to lock the « Settings » menu
Lock the « Options » menu in the « Settings » level
- Lock and don’t give access to the options in the « Settings » menu
Press to access to the following page of OPTIONS in the “INSTALLATION” menu
Create a parameter automatically for each sensor
- If this option is enabled, when adding a new sensor, a measurement parameter corresponding to the
type of sensor is created automatically. It’s still possible to modify and / or delete this parameter in a
second step.
For a « simple » installation this option allows a faster configuration.
Condition the flow rates only to the parameter
- This option is used to separate the flow rate condition and parameter control.
If this box is unchecked, the control is performed at the sensor level and for each controlled
parameter(s), it’s necessary to set the control levels separately. This allows, for example, to control
the dosing power differently from that of chlorine.
If this check box is checked, only one control level is set for all control parameters.
Condition the tank bottom volumes only to the parameter
- Same principle as the previous option but for the volume (level) sensors 4…20mA.
Activate the advanced configuration of the flow switch / meter
- If this box is checked, it’s possible to manage the condition type between the water circulation
detector and the flow meters to turn on or off the conditioning. The logical condition AND / OR is then
configurable in the “Conditions” menu.
If this box is unchecked the OR condition is active by default.
General configuration
Create a parameter automatically for each sensor
Condition the flow rates only to the parameter
Condition the tank bottom volumes only to the parameter
Activate the advanced configuration of the flow switch / meter
Installation options
(Page 2/2)
Activate the advanced configuration of the 4…20mA outputs
Let the choice of Insulated / Non-Insulated sensors