Installation Instructions

Technical characteristics and functions Page 13/67
Installation and starting instructions
Power output
1 12V power output ; 500mA
Communication port
RS485 1 RS485 communication port RS485
Ethernet 1 Ethernet output ETH
Protection of dosing outputs
Internal fuse 2 TR5 3,15 A 250 V Time delay fuses F1 & F2
Save
Button cell Type BR2032 Bat1
2) Main functions
Main functions
Fonction(s) Spécification(s) Remarque(s)
Regulation mode
P.I.D
Injection time calculated in %
240s relay injection cycle time.
Hysteresis
All or nothing
Type of actuators Power relay outputs Width modulation control
Direction of regulation
Up or down
Alarms Low and high alarms
Expressed in actual measurement value
High and low threshold control
Controlling
Floawrate control
Controlling injection to control wate
circulation.
Tank level
Controlling injection to control the level of
product to be injected.
Configuration Choice of standard configuration Automatic machine setup
Maintenance Maintenance assistance Control of regulatory device
3) Radio technologies in equipment
Radio technologies
Technologies Number of
antenna
Radiated powers Frequency bands of use
WIFI 1 < 20dBm
2400 MHz to 2483.5 MHz
2.4 GHz Band
Exclusion Band :
[2280 MHz – 2603.5 MHz]
4) Parameters and measurement scales
Measures and regulations
Parameters Measuring scale Customer measuring scale
Accuracy
Temperature
-5 to 45°C ± 0,5 %
0 to 100 °C ± 0,5 %
-10 to 100°C ± 0,5 %
pH
0 to 14 pH ± 0,5 %
1 to 12 pH ± 0,5 %
-1 to 15 pH ± 0,5 %
ORP
0 to 1000 mV ± 0,5 %
-1000 to 1000 mV ± 0,5 %
-1000 to 1000 mV ± 0,5 %
Free chlorine
0,01 to 0,5 mg/l ± 0,5 %
0,02 to 2 mg/l ± 0,5 %
0,05 to 5 mg/l ± 0,5 %
0,1 to 10 mg/l ± 0,5 %
0,2 to 20 mg/l ± 0,5 %
0,5 to 50 mg/l ± 0,5 %