Programming Instructions
Modbus communication register Page 34/40
41083
1 state_HI8 r BOOL 0=Out of range / 1=In range (Schedule)
41092
2 Timestamp Local r DWORD
Time since January 1 , 1970 00h00 [s]
Values and states
41101
1 device_state rw WORD Bit 0: device running
Bit 1: timer running
Bit 2: device strating up
Bit 3: device stopped due to timer
41201
2 param_E1_state rw DWORD
Cf. ParamState
41203
2 param_E1_measure_value
r REAL Measured value [unit of measure]
41205
2 param_E1_control_w rw REAL Regulation setpoint [unit of measure]
41207
2 param_E1_dosage_u r REAL Dosing control [1/1]
41209
2 param_E1_alarm_high rw REAL High alarm value [unit of measure]
(1) (2)
41211
2 param_E1_alarm_low rw REAL Low alarm value [unit of measure]
(1) (2)
41251
2 param_E2_state rw DWORD
Cf. ParamState
41253
2 param_E2_measure_value
r REAL Measured value [unit of measure]
41255
2 param_E2_control_w rw REAL Regulation setpoint [unit of measure]
41257
2 param_E2_dosage_u r REAL Dosing control [1/1]
41259
2 param_E2_alarm_high rw REAL High alarm value [unit of measure]
(1) (2)
41261
2 param_E2_alarm_low rw REAL Low alarm value [unit of measure]
(1) (2)
41301
2 param_E3_state rw DWORD
Cf. ParamState
41303
2 param_E3_measure_value
r REAL Measured value [unit of measure]
41305
2 param_E3_control_w rw REAL Regulation setpoint [unit of measure]
41307
2 param_E3_dosage_u r REAL Dosing control [1/1]
41309
2 param_E3_alarm_high rw REAL High alarm value [unit of measure]
(1) (2)
41311
2 param_E3_alarm_low rw REAL Low alarm value [unit of measure]
(1) (2)
41351
2 param_E4_state rw DWORD
Cf. ParamState
41353
2 param_E4_measure_value
r REAL Measured value [unit of measure]
41355
2 param_E4_control_w rw REAL Regulation setpoint [unit of measure]
41357
2 param_E4_dosage_u r REAL Dosing control [1/1]
41359
2 param_E4_alarm_high rw REAL High alarm value [unit of measure]
(1) (2)
41361
2 param_E4_alarm_low rw REAL Low alarm value [unit of measure]
(1) (2)
41401
2 param_E5_state rw DWORD
Cf. ParamState
41403
2 param_E5_measure_value
r REAL Measured value [unit of measure]
41405
2 param_E5_control_w rw REAL Regulation setpoint [unit of measure]
41407
2 param_E5_dosage_u r REAL Dosing control [1/1]
41409
2 param_E5_alarm_high rw REAL High alarm value [unit of measure]
(1) (2)
41411
2 param_E5_alarm_low rw REAL Low alarm value [unit of measure]
(1) (2)
41451
2 param_E6_state rw DWORD
Cf. ParamState
41453
2 param_E6_measure_value
r REAL Measured value [unit of measure]
41455
2 param_E6_control_w rw REAL Regulation setpoint [unit of measure]
41457
2 param_E6_dosage_u r REAL Dosing control [1/1]
41459
2 param_E6_alarm_high rw REAL High alarm value [unit of measure]
(1) (2)
41461
2 param_E6_alarm_low rw REAL Low alarm value [unit of measure]
(1) (2)
41501
2 param_E7_state rw DWORD
Cf. ParamState
41503
2 param_E7_measure_value
r REAL Measured value [unit of measure]
41505
2 param_E7_control_w rw REAL Regulation setpoint [unit of measure]
41507
2 param_E7_dosage_u r REAL Dosing control [1/1]
41509
2 param_E7_alarm_high rw REAL High alarm value [unit of measure]
(1) (2)