Programming Instructions
SYCLOPE ODITOUCH setting Page 15/40
Communication programming instructions
a) Modbus Configuration [1731]
Press to open following screen.
Modbus sur RS485
Mode RTU
- Selection of the modbus communication mode, on this selection button we find the
information of the selected mode (RTU) Press to change it.
Speed 19200
- Selection of the modbus communication speed, on this selection button we find the
information of the selected speed (19200). Press to change it.
Parity SANS
- Selection of the modbus communication parity, on this selection button we find the
information of the selected parity (SANS). Press to change it.
Stop bit(s) 2
- Information on the configuration of the number of stop bit(s). This option is not
configurable, it adapts according to the parity configuration and here is just information to
help you configure your connection.
Address 1
- Modbus address input of your regulator. Here the current value is (1).
Press it to open the numeric keypad and enter the desired value.
Possible adjustment from 1 to 247.
MODBUS
Modbus settings
Mode RTU
Modbus on RS485
Speed 19200
Modbus TCP
Stop bit(s) 2
Address
1
Parity WITHOUT
Peripheral WIFI
Port 502
Simultaneous connection(s) 1
Pseudo address 255