Programming Instructions

Programming screen « SETTINGS » Page 50/78
General programming instructions
5) Menu « Settings » - « SETPOINTS ALARMS » [0521]
« SETPOINTS ALARMS » menu will allow you to adjust the settings of the parameters of the
Biocides, inhibitor and dispersant.
Press to open following screen.
Parameter enables.
Press to edit
Measure Alarm or Setpoint with possible setting.
Press to open calibration screen.
Measure Alarm or Setpoint not configured
a) Bleed – Conductivity mode
Setpoint 1500 µs/cm
- Enter the conductivity setpoint value. Here the value is (1500).
Press to open the numeric keyboard and enter the desired value.
Possible adjustment from 0 to 20000 µS/cm
Hysteresis 500 µS/cm
- Enter the conductivity hysteresis value. Here the value is (500).
Press to open the numeric keyboard and enter the desired value.
Possible adjustment from 0 to 20000 µS/cm
Maximum bleed duration
- Security for bleed duration on conductivity bleed. You can setup here a maximum time duration for
conductivity reach the hysteresis point.
Possible adjustment from 0(OFF) to 1400 min
Post bleed lock duration
After each bleed, the system will lock each request of each organ during this time.
Possible adjustment from 0(OFF) to 1400 min
SETPOINTS
ALARMS
E02 - Conductivity
SETPOINT AND ALARMS SETTINGS
Bleed – Conductivity mode Measure Alarm
Setpoint
Hysteresis
E02 - Conductivity
E03 - Temperature
Maximum
bleed duration
E04 - Salinity
E05 -
Measure Setpoint
500
1500
OFF
µS/cm
µS/cm
min
Conductivity setpoint
1500
µ
S/cm
Post bleed
lock duration
OFF
min