Programming Instructions

Programming screen « SETTINGS » Page 48/78
General programming instructions
4) Menu « Settings » - « BIO-INHIB-DISP SETTINGS » [0421]
« BIO-INHIB-DISP SETTINGS » menu will allow you to adjust the settings of the parameters of the
Biocides, inhibitor and dispersant.
Press to open following screen.
1
The screen presents the settings that are configured. You can by pressing an active parameter change its
configuration. If it’s greyed out it means that the corresponding output is not enabled.
Parameter enables.
Press to edit
Parameter disables.
d) Biocide:
Pre bleed
- There are 2 possibilities for Pre bleed. The duration or the percent of hysteresis. It depends on the
pre bleed mode you have chosen in the “Outputs setting”.
- In the Duration case, press to open the numeric keyboard and enter the desired value.
Possible adjustment from 0 to 1440 min.
- In the Percent case, press to open the numeric keyboard and enter the desired value.
Possible adjustment from 0 to 100 %.
Duration of the post bleed action
- Enter the duration of the post bleed action value. Here the value is (5) min.
Press to open the numeric keyboard and enter the desired value.
Possible adjustment from 0 to 1440 min.
BIO-INHIB-DISP
SETTINGS
Biocide, Inhibitor and dispersant setting
Duration of the pre bleed
Percent of hyteresis for pre bleed
Duration of the post bleed action Duration of the post bleed action
Injection every
Injection every
For
For
Biocide A Biocide B
Dispersant
min
min
s
10
5
minute
20
Duration of the pre bleed
10
min
Injection every
Inhibitor (Continuous)