Programming Instructions
Programming screen « Setup menu » Page 43/78
General programming instructions
The screen shows the timers that are already configured and those not used. You can by pressing an
already configured clock, changing its configuration, or pressing an unused clock, configure its installation.
Timer already set.
Press to edit configuration
Timer not used.
Press to edit configuration
Force Power ON for biocide cycle
- If this case is selected, the controller will activate the relay when it need to inject biocide event if it’s
out of “normal” running cycle of the tower, and keep it activate during all the biocide cycle.
Finish active biocide cycle before Power OFF
- If this case is selected, when the operating timer arrive to the end of the active timer, if a biocide
cycle is in process, the controller keep the relay active until the end of the biocide cycle
Remote Control OFF stop operating timer
- If this case is selected, when the tower management remote control is remove during an operating
timer slot, the relay is disable event is the timer cycle is not finish.
Monday – Tuesday – Wednesday – Thursday – Friday – Saturday – Sunday
- Selection of the day(s) of the week timer will be active. Type of “multiple” selection, press desired
days to select/deselect. Here Monday – Wednesday – Friday are selected.
Start time 08:00 – End time 18:00 – Duration 405 min.
- You have 2 possibilities:
o Select Start time then End time and Duration will be automatically calculated.
o Select Start time then the Duration you want, and the End time will be automatically
calculated.
Press Start time and/or End time or Duration one after the other to open the numeric keyboard and
enter the desired value.
Time action every 5 week(s)
- Weeks recurrence selection. Here the value entered is (1), timer active every week. Type 2 for 1
week/2, 3 for 1 week/3 etc. Adjustment possible from 1 to 52
To save the timer press
To Delete a timer, enter in the timer, press and
M T W T F S S
5
10:00 – 17:15
M T W T F S S
1
- - - -
Timer setting
Operating timers 1
Mon Fri Tue Wed
Thu Sat Sun
Start time
End time
Duration
00 : 00 00 : 00 1440
5
Timer action every
d +1 min.
week(s)
Delete
Delete