Programming Instructions
Programming screen « Setup menu » Page 20/78
General programming instructions
c) CTFS input setting [2231]
Press to open the following screen.
SI1 - Conductivity - Temperature - Flow switch
- By checking or unchecking the check box you can choose to enable/disable the CTFS sensor. It’s
disabled by default.
Conductivity 100…10000µS
- Indicate the conductivity rating scale (100…10000µS) of the CTFS sensor. This scale is block and
unique.
Temperature 0…50°C
- Indicate the temperature rating scale (0…50°C) of the CTFS sensor. This scale is block and unique.
Starting delay time 2 minute(s)
- Enter the time during which the conductivity or temperature value should not be taken into account.
During activation of the CTFS sensor. Here it is (2) minutes.
Press to open the numeric keyboard and enter the desired value.
Adjustment possible from 0 to 480 minute(s)
Activation delay time 5 Second(s)
- Enter the time that the input must remain during its activation before the information is taken into
account. Here it is (5) seconds.
Press to open the numeric keyboard and enter the desired value.
Adjustment possible from 0 to 240 Second(s)
Deactivation delay time OFF Second(s)
- Same as before, but for reverse state.
SI1 - Conductivity - Temperature - Flow switch (CTFS) Enabled
CTFS input setting
SI1 - Conductivity - Temperature - Flow switch
Conductivity 100…10000µS
Sensor enabled
Temperature 0…50°C
Starting delay time
Starting delay time
minute(s)
minute(s)
2
2
Water Flow switch
Activation delay time
Deactivation delay time
5
OFF
second(s)
second(s)