Programming Instructions

Programming screen « Setup menu » Page 18/78
General programming instructions
b) Conductivity analog input setting [1231]
Press to open the following screen.
« Simple » view
RI2 – Conductivity Sensor enabled
- By checking or unchecking the check box you can choose to enable/disable the temperature sensor.
It’s disabled by default.
Scale 0…20mS/cm
- Select the sensor measurement scale, on this selection button you will find the information of the
currently selected scale (0…20mS/cm).
Press to change it.
Each sensor has a « Customer » scale. By selecting this scale, it is then possible to select the low and
high level of the scale and the unit of measurement. (See next screen)
Starting delay time OFF Minute(s)
- Enter boot delay (polarization). Here disabled for this type of sensor (OFF).
Press to open the numeric keyboard and enter the desired value.
Adjustment possible from 0 à 480 Minute(s).
K factor of the cell
- Enter the K factor of the cell. Here the value is blocked at 1.00 cm
-1
.
If you choose a « Customer » scale you have to enter the right K factor. (See next screen)
RI2 - Conductivity Enabled
Analog input setting
RI2 - Conductivity
Scale 0…20mS/cm
Starting delay time
minute(s)
Sensor enabled
OFF
K factor of the cell
cm
-1
1.00