Programming Instructions
Programming screen « Setup menu » Page 14/78
General programming instructions
Press to access to the “Setup options” page
Create a parameter automatically for each sensor
- If this option is enabled, when adding a new sensor, a measurement parameter corresponding to the
type of sensor is created automatically. It’s still possible to modify and / or delete this parameter in a
second step.
For a « simple » installation this option allows a faster configuration.
Activate the advanced configuration for flow switch & flow meter
- If this box is checked, it’s possible to manage the condition type between the water circulation
detector and the flow meters to turn on or off the conditioning. The logical condition AND / OR is then
configurable in the “Conditions” menu.
If this box is unchecked the OR condition is active by default.
Active the advanced configuration of the 4…20mA outputs
- This option, if checked, gives access to the « special » current settings. It’s then possible to define
the current generated in three special cases:
o Inhibition mode:
None
0 mA
Low range
3.4 mA
o Default mode:
0 mA
Low range
2.6 mA
o Range overflow mode
Maximum
20 mA
20.8 mA
Setup Options
Create a measure automatically for each sensor
Activate advance configuration for flow switch & flow meter
Activate advance configuration for 4…20mA outputs
Setup options
(Page 3/3)