Programming Instructions

Modbus communication register Page 32/40
Communication programming instructions
V. Modbus communication register
1) Address of Modbus registers
The registers are numbered in accordance with the Modbus standard. These are “HOLDINGS REGISTER” on the
range of registers from 40001 to 49999.
Some software and Modbus controllers use an address from 0 to 65535.
Modbus register 40001 therefore corresponds to Modbus address 0, register 40002 corresponds to address 1 and so
on and so forth.
Modbus
register
Number of
registers
Name Access Format Description
Interfaces
41001
2 signal_RI1 r
REAL
Signal on RI RI1 input [Ohm]
41003
2 signal_RI2 r
REAL
Signal on RI RI2 input [Ohm]
41005
2 signal_AI1 r
REAL
Current on input AI1 [mA]
41007
2 signal_AI2 r
REAL
Current on input AI2 [mA]
41009
2 signal_SI1 r
REAL
Conductivity on input SI [µS]
41011
2 signal_SI2 r
REAL
Temperature on input SI [°C]
41013
2 signal_K1 r
REAL
Signal on DIx input [Depends switch config]
41015
2 signal_K2 r
REAL
Signal on DIx input [Depends switch config]
41017
2 signal_MI1 r
REAL
Signal on MI1 input [Depends on module]
41019
2 signal_MI2 r
REAL
Signal on MI2 input [Depends on module]
41031
1 signal_DI1 r
BOOL
0=OPEN / 1=CLOSE
41032
1 signal_DI2 r
BOOL
0=OPEN / 1=CLOSE
41033
1 signal_DI3 r
BOOL
0=OPEN / 1=CLOSE
41034
1 signal_DI4 r
BOOL
0=OPEN / 1=CLOSE
41035
1 signal_DI5 r
BOOL
0=OPEN / 1=CLOSE
41036
1 signal_DIS r
BOOL
0=OPEN / 1=CLOSE (on input SI)
41041
1 state_PO1 r
BOOL
0=OPEN / 1=CLOSE
41042
1 state_FO1 r
BOOL
0=OPEN / 1=CLOSE
41043
1 state_FO2 r
BOOL
0=OPEN / 1=CLOSE
41044
1 state_FO3 r
BOOL
0=OPEN / 1=CLOSE
41045
1 state_FO4 r
BOOL
0=OPEN / 1=CLOSE
41046
1 state_RO1 r
BOOL
0=OPEN / 1=CLOSE
41056
2 signal_AO1 r
REAL
Signal on AO1 output [mA]
41058
2 signal_AO2 r
REAL
Signal on AO2 output [mA]
41076
1 state_HI1 r
BOOL
0=Out of range / 1=In range (Schedule Biocid A summer)
41077
1 state_HI2 r
BOOL
0=Out of range / 1=In range (Schedule Biocid A summer)
41078
1 state_HI3 r
BOOL
0=Out of range / 1=In range (Schedule Biocid A summer)
41079
1 state_HI4 r
BOOL
0=Out of range / 1=In range (Schedule Biocid A summer)
41080
1 state_HI5 r
BOOL
0=Out of range / 1=In range (Schedule Biocid A summer)
41081
1 state_HI6 r
BOOL
0=Out of range / 1=In range (Schedule Biocid A summer)
41082
1 state_HI7 r
BOOL
0=Out of range / 1=In range (Schedule Biocid A summer)
41083
1 state_HI8 r
BOOL
0=Out of range / 1=In range (Schedule Biocid A summer)
41084
1 state_HI9 r
BOOL
0=Out of range / 1=In range (Schedule Biocid A winter)
41085
1 state_HI10 r
BOOL
0=Out of range / 1=In range (Schedule Biocid A winter)
41086
1 state_HI11 r
BOOL
0=Out of range / 1=In range (Schedule Biocid A winter)
41087
1 state_HI12 r
BOOL
0=Out of range / 1=In range (Schedule Biocid A winter)