Programming Instructions

RS485 communication bus connections Page 10/40
Communication programming instructions
III. RS485 communication bus connections
COOLTouch
®
has an RS485 communication port to connect it to a computer equipped with a 485 port and
communication software to record the measurement values, alarms and different states of the device.
Connection to a computer USB port
Use a 3-wire cable.
Pass the cable through a cable gland.
Wire AA’ (n°3) of USB/485 converter to RS485 (A) (31).
Wire BB’ (n°4) of USB/485 converter to RS485 (B) (32).
Wire C (n°5) of USB/485 converter to PWR (C) (18)
Tighten the cable gland to seal.
Blue (Terminal n°3): AA’ RS485
White (Terminal n°4): BB’ RS485
Black (Terminal n°5): GND RS485
Configuration: All switches on "ON”
Contact us for more information about the product.
Respect the bus wiring.
A USB/RS485 converter is recommended to connect the SYCLOPE COOLTouch
®
to a computer. Please
refer to converter documentation to realize the connection.
Reference Name
INF1021 Converter USB => 485
Devices can be chained respecting the order of cables (Parallel wiring).