Installation Instructions
Technical characteristics and functions Page 12/57
Installation and starting instructions
III. Technical characteristics and functions
1) Technical characteristics
Main features
Type(s) Specification(s) Marker(s)
Consumption 6,5A Max (Without connected dosing accessories)
-
Power supply requirements
100 - 240 VAC (± 10%) 50/60Hz
-
Electrical protection
Fuse 550mA, Reset by power interruption
F4 & F5
Operating temperature (°C) -5 °C to 45 °C (23 °F to 113 °F) -
Case material Polycarbonate -
Dimensions of the case
Length: 280 mm (11 inches)
Width: 219 mm (8.6 inches)
Height: 156 mm (6.1 inches)
-
Case weight empty 0,850 kg -
Indicator light (LED) Group 0
Display 5-inch color LCD screen Resistive touch -
Environment
Storage temperature -10 °C to 70 °C (10 °F to 158 °F) -
Max operating altitude 2000 meters
Humidity Max. 90% without condensation -
Protection rating IP 65 -
Product certification CE -
Max overvoltage category of
the power supply network
CAT II
Pollution degree DP 2
Electromagnetic
compatibility
Class B disruption tests comply with EN61326-1
Class B disruption tests comply with EN61326-2-6
Class B disruption tests comply with EN55011
Harmonics tests comply with EN61000-3-2
Harmonics tests comply with EN61000-3-3
Immunity tests comply with EN61000-4-2
Immunity tests comply with EN61000-4-3
Immunity test EN61000-4-4
Immunity tests comply with EN61000-4-5
Immunity tests comply with EN61000-4-6
Immunity tests comply with EN61000-4-8
Immunity tests comply with EN61000-4-11
-
Standard
EN 61000 Electromagnetic compatibility (CEM)
EN 61326 Electrical measuring, control and laboratory equipment
for a standard environment (class B home use)
-
Inputs
RTD (Pt100 / Pt1000)
1 isolated input (Impedance Pt100 : 100 to 138 Ω ; Pt 1000 :
1000 to 1385 Ω)
RI1
Contictivity input 1 isolated input (Impedance 40Ω to 1MΩ) RI2
4-20mA Inputs
2 Isolated inputs 24VDC no-load
(0 to 25 mA ; Insulation 35VDC ; Impedance 160Ω)
AI1 & AI2
Digital inputs 5 inputs (0 ro 12 VDC ; Non-isolated ; Impedance 5kΩ) DI1 to DI5
Serial input 1 input UART 5V TTL SI1
USB inputs
USB connector on front (Exclusive use of USB key for Firmware
Update) (5VDC ; 500mA)
-
Outputs
Relay outputs 1 self-powered relay output 3A Max ; 240VAC Max PO1
Relay outputs 4 ON/OFF relay outputs 3A Max ; 48VAC Max FO1 to FO4