Specifications

Connect quick coupler
d) Active high signal:
Start with coupler in closed mode [A].
Measure between connection and ground(GND).
The value should be 0 V.
Switch to open mode [B]
When the signal is active high, the value should
be between 8-36 V.
e) Active low signal:
Start with coupler in closed mode [A].
Measure between connection and ground(GND).
The value should be 8-36 V.
Switch to open mode [B].
The value should be 0 V.
3. Remove existing cable from the machine’s
original quick coupler.
4. Connect cable end marked GPI1, flat pin
FSH1, to the machine original quick coupler[2].
5. Connect existing cable to flat pin FS1[2].
6. Place enclosed diode in the holder for GPI1
[3].
IMPORTANT
Place the diode in correct direction with respect to the
poles, active high signal and acitve low signal respec-
tively. See image below.
7. If quick coupler for TR-system does not exist,
please ignore steps 8 - 12.
8. Identify signal from the tiltrotator quick cuopler
(active high/active low).
9. Remove existing cable from the quick coupler.
Quantum
19