6 Technical data
6.5 Volumetric flow ranges
The measuring ranges are stated under the following conditions:
• Standard flow in air
• Reference pressure: 1000 hPa
• Reference temperature: 20°C
Inch DN Inner
diameter
(mm)
S402-S
(m³/h)
S402-M
(m³/h)
1" DN25 27.3 0.5 ... 147.7 0.6 ... 294.7
1¼" DN32 36.0 0.9 ... 266.3 1.2 ... 531.5
1½" DN40 41.9 1.2 ... 366.7 1.5 ... 731.9
2" DN50 53.1 2.0 ... 600.1 2.5 ... 1197.6
2½" DN65 68.9 3.5 ... 1026.5 5.0 ... 2048.6
3" DN80 80.9 5.0 ... 1424.4 7.0 ... 2842.7
4" DN100 100.0 10 ... 2183.3 12 ... 4357.2
5" DN125 125.0 13 ... 3419.6 18 ... 6824.4
6" DN150 150.0 18 ... 4930.1 25 ... 9838.9
8" DN200 200.0 26 ... 8785.6 33 ... 17533.3
10" DN250 250.0 40 ... 13743.9 52 ... 27428.5
12" DN300 300.0 60 ... 19814.8 80 ... 39544.1
NOTE:
To calculate flow ranges based on pipe and reference conditions in your
site, download and install the "Flow range calculator" tool for free from
http://www.suto-itec.com.
To fast access the tool download page, enter "flowrange" (without
spaces) in the search field and click the search result.
S402 11