Sensor signal outputs
Variant 2:
8.3 Modbus output
Mode : RTU
Baud rate : 19200
Device address : 1
Framing / parity / stop bit : 8, N, 1
Response timeout : 1 second
Response delay : 0 ms
Inter-frame spacing : 7 char
Remarks
• Modbus communication settings can be changed by the service
appS4C-FS.
Index
Channel
description
Resolution Format Length
Modbus
address
1 Flow 0.1 FLOAT 4-byte 6
2 Consumption 1 UNIT32 4-byte 8
3 Temperature 0.1 FLOAT 4-byte 0
4 Pressure 0.01 FLOAT 4-byte 2
Remarks
• All numbers are in little-endian format.
• Function code: 03.
• The measurement value is always available in the programmed
physical unit.