4. Technical data
4.2 Electrical data
Power supply 15 ... 30 VDC, 200 mA
4.3 Output-signals
Analogue output Signal: 4 ... 20 mA, isolated
Scaling: 0 to max flow
Max load: 250R
Pulse output 1 pulse per consumption unit, isolated switch,
max. 30 VDC, 200 mA (pulse length: 10 ... 120
ms, depends on flow rate)
Modbus output See chapter 9.3
4.4 Accuracy
Accuracy* ±(1.5% of reading + 0.3% FS) (optional 1% of
reading)
Temperature drift: < 0.05%/K
Stated accuracy at Ambient/process temperature 23°C ± 3°C
Ambient/process humidity <90%
Process pressure at 0.6 Mpa
Repeatability ± 0.25% of reading
*Specified accuracy is valid only within the minimum and maxmim flow
rates that are indicated in section 4.5.
4.5 Volumetric flow ranges
Inch DN Di
(mm)
S401-S
(m³/h)
S401-M
(m³/h)
S401-H
(m³/h)
½" DN15 - - -
¾" DN20 - - -
1" DN25 27.3 0.5 ... 147.7 0.6 ... 294.7 0.6 ... 356.9
1¼" DN32 36.0 0.9 ... 266.3 1.2 ... 531.5 1.2 ... 643.5
1½" DN40 41.9 1.2 ... 366.7 1.5 ... 731.9 1.5 ... 886.2
2" DN50 53.1 2.0 ... 600.1 2.5 ... 1197.6 3 ... 1450.0
2½" DN65 68.9 3.5 ... 1026.5 5.0 ... 2048.6 5 ... 2480.4
3" DN80 80.9 5.0 ... 1424.4 7.0 ... 2842.7 7 ... 3441.9
S401 9