Operation Manual
Table Of Contents
- 1. Safety instructions
- 2. Application
- 3. Features
- 4. Technical data
- 5. Dimensional drawing
- 6. Determination of the installation point
- 7. Inlet and outlet sections
- 8. Sensor installation
- 9. Sensor signal outputs
- 10. Sensor display (option)
- 11. Service App S4C-FS
- 12. Calibration
- 13. Maintenance
- 14. Disposal or waste
- 15. Warranty
- 16. Appendix A - Analogue output
- 17. Appendix B - Modbus communication example
- 18. Appendix C - LRC and CRC calculation
17. Appendix B - Modbus communication example
16 (0x10) Write multiple registers
Request Response
Slave address 1 byte Slave address 1 byte
Function code 1 byte Function code 1 byte
Starting address
Hi
1 byte Starting address
Hi
1 byte
Starting address
Lo
1 byte Starting address
Lo
1 byte
No. of registers
Hi
1 byte No. of registers
Hi
1 byte
No. of registers
Lo
1 byte No. of registers
Lo
1 byte
Byte count 1 byte CRC 2 bytes
Data Hi 1 byte
Data Lo 1 byte
: :
Data Hi 1 byte
Data Lo 1 byte
CRC 2 bytes
17 (0x11) Report slave ID
Request Response
Slave address 1 byte Slave address 1 byte
Function code 1 byte Function code 1 byte
CRC 2 bytes Byte count 1 byte
Slave ID 2 bytes
Device run
indicator
2 bytes
Product code 2 bytes
Product name 20 bytes
CRC 2 bytes
34 S401