Operation Manual

9. Sensor signal outputs
9.3 Modbus output
Mode : RTU
Baud rate : 19200
Device address : 1
Framing / parity / stop bit : 8, N, 1
Response time : 1 second
Response delay : 0 ms
Inter-frame spacing : 7 char
Remarks
Modbus communication settings can be changed by the service
software.
Index Channel description Resolution Format Length
Modbus
address
1 Flow 0.1 FLOAT 4 Byte 6
2 Consumption 1 UNIT32 4 Byte 8
3 Temperature 0.1 FLOAT 4 Byte 0
4
Reverse consumption
1 UNIT32 4 Byte 14
5
Flow Direction Indication
1 UNIT32 4 Byte 42
Remark
All numbers are in the little-endian format.
Function code: 03.
Different units have different resolutions.
The measurement value is always available in the programmed physical
unit.
Flow direction Flow direction indication
Forward 0
Reverse 1
S401 25