User manual

30
31
OPzV GEL ABSORPTION CHARGE TIME
Where: T = 0.38 x C /I T = ABSORPTION CHARGE TIME
C = 20 hr RATED CAPACITY (total AH capacity of battery bank)
I = Charging Current (Amps) (*see Note: CHARGING CURRENT on pg 11 for details)
0.38 = (factors in assumed current loss during Absorption charge phase)
EXAMPLE:
1 string of 2-Volt S2-690GEL models
C = 20 hr AH rate = 785 AH
I = 20% (recommended) of 785 AH = 157 Amps
T = 0.38 x 785/157 = 1.9 hrs
OPzV GEL FLOAT STAGE AND TERMINATION
To maintain the battery bank at 100% SOC, the charger continues to apply a Float
charge to the battery bank at the End Amps/Return Amps/Tail Current indefinitely
or until the charger is shut off or unplugged.
OPzV GEL REFRESH CHARGE
If Rolls OPzV GEL batteries are properly charged they should not experience
varied capacity loss or require balancing. If they were not properly charged and
there is a decrease in capacity, fully recharge the batteries at the recommended
voltage. It is important to prevent heavy-discharge. If the batteries will be stored for
extended periods of time, apply a periodic refresh charge. Frequency will depend
on storage temperature as noted:
DISPOSAL PROCEDURE
Batteries must NEVER be disposed of in household waste. To reduce environmental impact,
bring your spent OPzV GEL batteries to a certified recycling depot to be recycled.
OPzV GEL BATTERY CAPACITY & TEMPERATURE
Ideal operating temperature for OPzV GEL batteries is 25°C (77°F). Note that higher
operating temperatures will reduce cycle life due to cell degradation. Cycle life loss
is not recoverable.
Ex. Continuous operation at 35°C (95°F) will typically reduce cycle life by 50%.
Cooler operating temperatures will reduce battery capacity. Capacity is regained as
operating temperatures rise. To calculate the adjusted capacity, refer to Table 3 :
Cold Temperature Capacity Multiplier
NOTE:
If actual measured current is
120 Amps, or the maximum
charger output is limited to
120 Amps, 120 is used.
(Ex. 2 x 60 Amp controllers)
T = 0.38 x 785/120 = 2.5 hrs
Storage Temperature Refresh Charge Interval
Below 20ºC (68ºF) 9 Months
20ºC (68ºF) - 30ºC (86ºF) 6 Months
Higher than 30ºC (86ºF) 3 Months
TABLE 9: OPzV GEL Storage Temperature & Refresh Charge