VRLA AGM CHARGE EFFICIENCY/CHARGE FACTOR
Charge efficiency is a measure of the energy you may take out of a charged battery
divided by the energy required to charge it. Charge efficiency will depend on a
number of factors including the rate of charging or discharging. VRLA AGM batteries
have an average charge efficiency of ~80%. This should be reduced 1% per year
after the third (3) year of operation.
VRLA AGM REFRESH CHARGE
If Rolls VRLA AGM batteries are properly charged they should not experience varied
capacity loss or require balancing. If they were not properly charged and there is
a decrease in capacity, fully recharge the batteries at the recommended voltage. It
is important to prevent heavy-discharge. If the batteries will be stored for extended
periods of time, apply a periodic refresh charge. Frequency will depend on storage
temperature as noted below.
STORAGE
NOTE: When not in use, it is normal to expect 2% self-discharge per month (at 25ºC
(77ºF) for sealed VRLA AGM models. This rate slows as ambient temperatures
decrease and increases at higher temperatures. Stored batteries should be recharged
every 3-4 months until the battery is put in service to avoid sulfation buildup and
possible freezing in cold temperatures.
DISPOSAL PROCEDURE
Batteries must NEVER be disposed of in household waste. To reduce environmental impact,
bring your spent VRLA AGM batteries to a certified recycling depot to be recycled.
VRLA AGM BATTERY CAPACITY & TEMPERATURE
Ideal operating temperature for VRLA AGM batteries is 25°C (77°F). Note that higher
operating temperatures will reduce cycle life due to cell degradation. Cycle life loss
is not recoverable.
Ex. Continuous operation at 35°C (95°F) will typically reduce cycle life by 50%.
Cooler operating temperatures will reduce battery capacity. Capacity is regained as
operating temperatures rise. To calculate the adjusted capacity, refer to Table 3 :
Cold Temperature Capacity Multiplier
Storage Temperature Refresh Charge Interval
Below 20ºC (68ºF) 9 Months
20ºC (68ºF) - 30ºC (86ºF) 6 Months
Higher than 30ºC (86ºF) 3 Months
TABLE 7: VRLA AGM Storage Temperature & Refresh Charge