User manual

24
25
VRLA AGM ABSORPTION CHARGE TIME
Where: T = 0.38 x C /I T = ABSORPTION CHARGE TIME
C = 20 hr RATED CAPACITY (total AH capacity of battery bank)
I = Charging Current (Amps) (*see Note: CHARGING CURRENT on pg 11 for details)
0.38 = (factors in assumed current loss during Absorption charge phase)
EXAMPLE:
2 strings of 6 Volt S6-460AGM models
C = 20 hr AH rate = 415 AH x (2 strings) = 830 AH
I = 20% (recommended) of 830 AH = 166 Amps
T = 0.38 x 830/166 = 1.9 hrs
VRLA AGM FLOAT STAGE AND TERMINATION
To maintain 100% SOC, the charger continues output to the battery bank at the
programmed Float voltage and End Amps/Return Amps/Tail Current indefinitely or
until the charger is shut off or unplugged. The profile in Table 6: VRLA AGM
Charge Voltage may be used with or without the Float stage. Without the Float
stage, recharge may be terminated based on time. This will vary by depth of
discharge and charge current, or percentage recharge (105-110%).
ROLLS VRLA AGM BATTERY CHARGE
VOLTAGE PARAMETERS
NOTE: Use the highlighted voltage set points when charge equipment is supplied
with a temperature sensor. Set at 4mV/ºC/Cell...(+/- 96mV per ºC from a 2C
Delta - 48V System) Higher or lower settings may cause incorrect adjustments
in charge voltage. Without a temperature sensor, charge settings must be
adjusted manually based on the battery temperature when in use, not just
ambient temperatures.
TABLE 6: VRLA AGM Charge Voltage
NOTE:
If actual measured current is
120 Amps, or the maximum
charger output is limited to
120 Amps, 120 is used.
(Ex. 2 x 60 Amp controllers)
T = 0.38 x 830/120 = 2.6 hrs