User Guide

XR315IN-510
25
9 Specifications
Operational Voltage Range: 90 to 150 Volts AC
Current rating: 15 Amps
Power Rating: 1,800 Watts
Maximum Load Inrush Energy: 1400 Joules total during power-up
Surge Let-through Voltage: Zero let-through Voltage for a 6000 Volt surge
Meets Federal Guidelines: Grade A, Class 1, Mode 1 (CID A-A-55818)
EMI/RFI Filter, Normal Mode: 40 dB @ 100 KHz, 50dB @ 300 KHz, 50 dB @ 3 MHz, 50 dB @ 30
MHz (50 Ohm load)
EMI/RFI Filter, Common Mode: 18dB @ 300 KHz, 30 dB @ 1 MHz, 50 dB @ 5 MHz, 50 dB @ 20
MHz (50 Ohm load)
Maximum Applied Surge Voltage: 6,000 Volts *
Maximum Applied Surge Current: Unlimited (due to current limiting) *
Maximum Applied Surge Energy: Unlimited (due to current limiting) *
Endurance: (C62.41-1991 category B3 pulses), 1 KV > 500,000;
3 KV > 10,000; 6 KV > 1000
Number of Outlets: 8
Remote Control Voltage: 5 to 30 Volts DC
Remote Control Current Draw: 4 mA maximum
Contact Closure Max. Resistance: 100 Ohms
Auxiliary Relay Contact Rating: 30 Volts DC at 1 Amp
12 Volt Output Max. Current: 40 mA
AC Voltmeter Accuracy: ± 2%
AC Ammeter Accuracy: 0.1A resolution, ±1A accuracy
Coax Protection: Compatible with Cable Television (CATV), Digital Satellite System
(DSS), Television, Video Cassette Recorder (VCR), Cable Modem,
and TV Antenna Equipment. Approvals: UL 497B, UL Recognized.
Dimensions (no rack ears or feet): 17.3” W x 10.5” D x 1.7” H
Weight: 12 lbs (5.4kg)
Temperature Range: 5C to 35C
Humidity Range: 5% to 95% R.H. Non-condensing
Agency Listings: ETL and cETL (UL 1449, Third Edition, Type 3 Surge Protective Device; UL 1283;
CSA C22.2 No.8-M1986, R2004)
* 1.2 x 50 microsecond industry standard combination wave surge as per IEEE C62.41